Emerson 225-600KVA installation manual Front View

Page 22

Installation Drawings

Figure 14 Liebert NX Stand-Alone Junction Cabinet terminal wiring

.56 (14)

 

 

.56

.56

 

 

 

Typ

2.2 (55)

(14) Typ

(14) Typ

1.7 (44) X 0.7 (18)

 

 

 

 

16 Places

1.8 (45)

 

Slot 16 Places

2.2 (55)

 

 

 

16 Places

Typ. Each Busbar

 

 

 

 

 

2.2 (55)

18 Places

 

 

 

 

 

 

 

 

 

 

 

16 Places

 

 

2.2 (55)

 

 

 

 

 

 

18 Places

2.2 (55)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18 Places

 

 

 

Ground Bus

Negative Bus

Positive Bus

 

 

30.9 (785)

 

 

33.5 (805)

 

 

 

 

 

Positive

 

 

 

 

 

 

 

Bus

 

 

 

 

 

 

 

Ground

 

 

 

 

 

 

 

Bus

 

 

 

76.9

 

 

 

41.3

 

 

 

(1952)

 

 

 

 

 

 

 

 

 

(1050)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Negative

 

 

 

 

 

 

 

Bus

 

 

 

 

 

 

 

13.7

 

 

 

 

 

 

 

(348)

 

 

 

7.4

8.7

9.0

 

 

Right Side

13.6

(189)

(221)

(228)

 

 

Front View

 

 

View

(346)

 

 

 

Do not double stack lugs (two lugs on same side of busbar). This is to prevent the cables from coming into contact with other busbars.

Lugs

Bolt Busbar

DUAL LUG

CONNECTION DETAIL

Notes:

1.All dimensions are in inches (mm).

2.Control wiring and power wiring must be run in separate conduit.

3.Aluminum and copper-clad aluminum cables are not recommended.

4.Widths are without side panels. The width is 32.1" (815mm) with side panels. 5.The depth dimension includes the front door and rear panel.

Liebert® NX

18

Image 22
Contents Liebert NX Battery System Product Warranty Registration Table of Contents Figures Important Safety Instructions Liebert NX Preliminary Checks IntroductionEnvironmental Considerations Shipping bolts-Top-Terminal Battery Cabinet PositioningSystem Composition ClearancesSafety LayoutJunction Battery Attached Liebert Additional Junction BatteryAdditional Liebert Attached Additional Liebert Battery Cabinet Stand Alone Junction Power ConnectionCable Entry Control Connection GroundingExternal Battery Room Temperature Sensor-Optional Alber Monitoring System-OptionalBottom View Main components, Liebert Top-Terminal Battery Cabinet Do not DOUBLE-STACK Lugs Front Top View Front Ground BUS Detail Front View Terminal Details Outline DrawingLiebert NX Battery Cabinet control wiring Attached battery cabinet connections Typical Alber battery monitoring connections Battery Alber battery monitoring assembly diagram Alber battery monitoring assembly connectionsTop-Terminal battery configuration Cable Interconnect Diagram Left-Side Busbar Connections Right-Side Busbar Connections Specifications Liebert NX Battery Cabinet specificationsAlber battery monitoring option specifications Liebert NX Junction Cabinet specificationsDC currents for Liebert NX modules Liebert NX Battery Cabinet internal breaker Liebert NX Battery Cabinet approximate weightsBattery torque values UPS Rating KVA # Conduit Size, Ph, GTorque specifications, unless otherwise labeled Specifications Liebert NX Specifications Liebert NX Page Twor k Ne tIs t Care