Specifications
4.0SPECIFICATIONS
Table 2 | Liebert NX Battery Cabinet specifications |
|
| ||
|
|
|
|
| |
|
|
| Values | ||
|
|
|
| ||
Battery Cabinet Parameters |
| ||||
| Battery Type | VRLA (Valve Regulated Lead Acid) | |||
|
|
|
| ||
| Nominal Battery Bus, VDC |
| 480V | ||
|
|
|
| ||
| Battery Float Voltage, VDC |
| 540V | ||
|
|
| |||
| Minimum EOD Voltage, VDC | 384V (for VRLA / Flooded Lead Acid) | |||
|
| ||||
Battery Discharging Max current (EOD), A | See Table 5 | ||||
|
|
|
| ||
Physical Parameters and Standards |
|
|
| ||
| Width, in. (mm) 1 | 56.5 (1435) |
| 63.0 (1600) | |
| Depth, in. (mm) 2 | 33.5 (850) |
| 33.5 (850) | |
| Height, in. (mm) | 76.8 (1950) |
| 76.8 (1950) | |
|
|
|
|
| |
| Weight, lb (kg) approx. |
| Table 7 | ||
|
|
| |||
| Standard Color | Black | |||
|
|
| |||
| Front Door Opening (for serviceability) | More than 180° | |||
|
|
| |||
| Degree of Protection for UPS Enclosure | IP 20 (with and without front door open) | |||
|
|
| |||
| Minimum Clearance, Top | 24" (610mm) | |||
|
|
|
| ||
| Minimum Clearance, Back |
| 0" | ||
|
|
|
| ||
| Minimum Clearance, Sides |
| 0" | ||
|
|
| |||
| Cable Entrance | Top or Bottom | |||
|
|
| |||
Standards & Conformities | UL 1778; CSA 22.2 107.3 | ||||
FCC Part 15, Class A; ISTA Procedure 1H; WEEE | |||||
|
| ||||
Environmental |
|
|
| ||
|
|
|
| ||
| Storage Temperature Range, °F (°C) | ||||
| 74°F to 80°F | ||||
|
| ||||
| Operating Temperature Range, °F (°C) | 32°F to 104°F (0 to 40°C) | |||
| 74°F to 80°F | ||||
|
| ||||
| Relative Humidity | up to 95% | |||
| (Operating and | ||||
|
| ||||
| Maximum Altitude Above MSL, ft (m) | 4920 (1500) (as per IEC 62040/3) - | |||
| 1% Maximum kW derate / 100m rise between | ||||
|
|
1.Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels.
2.Depth dimensions include the front door and rear panel.
Liebert® NX™ | 28 |