Emerson 225-600KVA installation manual Positioning, Shipping bolts-Top-Terminal Battery Cabinet

Page 8

Mechanical Installation

1.4Positioning

The cabinet is structurally designed to handle lifting from the base.

Power terminals, auxiliary terminals blocks and power switches are accessed from the front and top.

Removable panels on the top are secured to the chassis by screws. The door can be opened to give access to the power connections bars, auxiliary terminal blocks and power isolators. The front door can be opened 180° for easier service and more flexibility in installation.

1.4.1Moving the Cabinets

The route to be travelled between the point of arrival and the unit’s installation location must be planned to make sure that all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check that doorways, lifts, ramps, etc., are adequate and that there are no impassable corners or changes in the level of corridors).

Ensure that the cabinet weight is within the designated surface weight loading (kg/cm2) of any handling equipment. See Table 2 for weight details.

Ensure that any lifting equipment used to move the battery equipment has sufficient lifting capacity. Battery system equipment can be handled by a forklift or similar equipment.

Because the weight distribution in the cabinet is not symmetrical, use extreme care during handling and transporting.

When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15° tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath the unit.

Handling the unit with straps is not authorized.

! WARNING

Risk of heavy unit falling over. Can cause equipment damage, injury and death.

Exercise extreme care when handling battery cabinets. The battery system cabinets weigh from 3760 to 8990 lb. (1706 to 4078kg).

Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.

Slots at the base of the cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit.

The cabinet with top terminal batteries ships with extra bolts installed on the interior doors. Once the cabinet is in the final position, these bolts can be removed. See Figure 1

Figure 1 Shipping bolts—Top-Terminal Battery Cabinet

Shipping

 

Bolts

 

 

Shipping

Shipping

Bolts

Bolts

 

 

* Outer doors removed

Shipping

for clarity

Bolts

 

Shipping

Shipping

Bolts

Bolts

 

 

Shipping

Shipping Bolts

Bolts

Liebert® NX

4

Image 8
Contents Liebert NX Battery System Product Warranty Registration Table of Contents Figures Important Safety Instructions Liebert NX Environmental Considerations IntroductionPreliminary Checks Shipping bolts-Top-Terminal Battery Cabinet PositioningSystem Composition ClearancesSafety LayoutAdditional Liebert Attached Attached Liebert Additional Junction BatteryJunction Battery Cable Entry Power ConnectionAdditional Liebert Battery Cabinet Stand Alone Junction Control Connection GroundingExternal Battery Room Temperature Sensor-Optional Alber Monitoring System-OptionalBottom View Main components, Liebert Top-Terminal Battery Cabinet Do not DOUBLE-STACK Lugs Front Top View Front Ground BUS Detail Front View Terminal Details Outline DrawingLiebert NX Battery Cabinet control wiring Attached battery cabinet connections Typical Alber battery monitoring connections Battery Alber battery monitoring assembly diagram Alber battery monitoring assembly connectionsTop-Terminal battery configuration Cable Interconnect Diagram Left-Side Busbar Connections Right-Side Busbar Connections Specifications Liebert NX Battery Cabinet specificationsDC currents for Liebert NX modules Liebert NX Junction Cabinet specificationsAlber battery monitoring option specifications Liebert NX Battery Cabinet internal breaker Liebert NX Battery Cabinet approximate weightsBattery torque values UPS Rating KVA # Conduit Size, Ph, GTorque specifications, unless otherwise labeled Specifications Liebert NX Specifications Liebert NX Page Ne t Is tTwor k Care