Emerson 225-600KVA installation manual Battery torque values, UPS Rating KVA # Conduit Size, Ph, G

Page 35

Specifications

Table 8

Recommended conduit and cable sizes from Liebert NX UPS to DC supply

 

 

 

UPS Rating

 

 

kVA

 

(#) Conduit Size, Ph, G

 

225

 

(2); 2C; 2-500kcmil, #1/0AWG

 

 

 

 

 

250

 

(2); 2C; 2-600kcmil; #1/0AWG

 

 

 

 

 

300

 

(2); 2.5C; 2-600kcmil; #2/0AWG

 

 

 

 

 

400

 

(3); 2.5C; 2-600kcmil; #3/0AWG

 

 

 

 

 

500

 

(3); 2.5C; 2-750kcmil; #4/0AWG

 

 

 

 

 

600

 

(5); 2.5C; 2-600kcmil; 250kcmil

 

 

 

 

 

The recommendations in this table are guidelines only and are superseded by local regulations and codes of practice where applicable:

1.Recommended cable sizes are 75C (THW) wire at 86°F (30°C) ambient.

2.For continuous operations not at 86°F (30°C), Emerson recommends selecting the appropriate cable type based on the particular installation requirements.

3.The ground conductor should be sized according to the fault rating, cable lengths, type of protection, etc. The ground cable connecting the UPS to the main ground system must follow the most direct route possible.

4.When laying the power cables, do not form coils. Coiling power cables increases the likelihood of electromagnetic interference.

Table 9

Battery torque values

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

Torque Value

Code

 

Manufacturer

 

Battery Model

in-lb (Nm)

PR

 

 

 

UPS12-300MR

110

(12.4)

 

 

 

 

 

 

 

RR

 

 

 

UPS12-350MR

110

(12.4)

UR

 

C&D Batteries

 

UPS12-400MR

110

(12.4)

 

 

 

 

 

 

 

WS

 

 

 

UPS12-490MRLP

110

(12.4)

 

 

 

 

 

 

 

XR

 

 

 

UPS12-540MR

110

(12.4)

PX

 

 

 

HX300-FR

65

(7.3)

 

 

 

 

 

 

 

RX

 

 

 

HX330-FR

65

(7.3)

 

 

 

 

 

 

 

UX

 

 

 

HX400-FR

65

(7.3)

WX

 

Enersys

 

HX500-FR

65

(7.3)

 

 

 

 

 

 

 

XX

 

 

 

HX540-FR

65

(7.3)

 

 

 

 

 

 

 

2K

 

 

 

16HX800F

100

(11.3)

4K

 

 

 

16HX925F

100

(11.3)

 

 

 

 

 

 

 

QA

 

 

 

27HR3500

65

(7.3)

 

 

 

 

 

 

 

SA

 

East Penn

 

31HR4000

65

(7.3)

WA

 

 

31HR5000

65

(7.3)

 

 

 

 

 

 

 

 

 

 

YA

 

 

 

HR5500

65

(7.3)

 

 

 

 

 

 

 

31

Liebert® NX

Image 35
Contents Liebert NX Battery System Product Warranty Registration Table of Contents Figures Important Safety Instructions Liebert NX Environmental Considerations IntroductionPreliminary Checks Positioning Shipping bolts-Top-Terminal Battery CabinetClearances System CompositionLayout SafetyAdditional Liebert Attached Attached Liebert Additional Junction BatteryJunction Battery Cable Entry Power ConnectionAdditional Liebert Battery Cabinet Stand Alone Junction Grounding Control ConnectionAlber Monitoring System-Optional External Battery Room Temperature Sensor-OptionalBottom View Main components, Liebert Top-Terminal Battery Cabinet Do not DOUBLE-STACK Lugs Front Top View Front Ground BUS Detail Front View Outline Drawing Terminal DetailsLiebert NX Battery Cabinet control wiring Attached battery cabinet connections Typical Alber battery monitoring connections Battery Alber battery monitoring assembly connections Alber battery monitoring assembly diagramTop-Terminal battery configuration Cable Interconnect Diagram Left-Side Busbar Connections Right-Side Busbar Connections Liebert NX Battery Cabinet specifications SpecificationsDC currents for Liebert NX modules Liebert NX Junction Cabinet specificationsAlber battery monitoring option specifications Liebert NX Battery Cabinet approximate weights Liebert NX Battery Cabinet internal breakerUPS Rating KVA # Conduit Size, Ph, G Battery torque valuesTorque specifications, unless otherwise labeled Specifications Liebert NX Specifications Liebert NX Page Care Ne tIs t Twor k