Xantrex Technology XPF 35-10 manual Connection to the Load, Remote Sensing, Protection

Page 11

Connection to the Load

The load should be connected to the positive (red) and negative (black) OUTPUT terminals. Both are fully floating and either can be connected to ground.

Remote Sensing

The unit has a very low output impedance, but this is inevitably increased by the resistance of the connecting leads. At high currents this can result in significant differences between the indicated source voltage and the actual load voltage (two 20mconnecting leads will drop 0.2V at 5 Amps, for instance). This problem can be minimised by using short, thick, connecting leads, but where necessary it can be completely overcome by using the remote sense facility.

This requires the sense terminals to be connected to the output at the load instead of at the source; insert wires into the spring-loaded SENSE terminals and connect directly to the load. Switch the LOCAL/REMOTE switch to REMOTE. To avoid instability and transient response problems, care must be taken to ensure good coupling between each output and sense lead. This can be done either by twisting the leads together or by using coaxially screened cable (sense through the inner). An electrolytic capacitor directly across the load connection point may also be beneficial.

The voltage drop in each output lead must not exceed 0.5 Volts.

Switch the LOCAL/REMOTE switch back to LOCAL when remote sensing is not in use.

Series or Parallel connection with other units

The outputs of the power supply are fully floating and may be used in series with other power supply units to generate high DC voltages up to 300V DC.

WARNING! Such voltages are exceedingly hazardous and great care should be taken to shield the output terminals for such use. On no account should the output terminals be touched when the unit is switched on under such use. All connections to the terminals must be made with the power switched off on all units.

It should be noted that the unit can only source current and cannot sink it, thus units cannot be series connected in anti-phase.

The unit can be connected in parallel with others to produce higher currents. Where several units are connected in parallel, the output voltage will be equal to that of the unit with the highest output voltage setting until the current drawn exceeds its current limit setting, upon which the output will fall to that of the next highest setting, and so on. In constant current mode, units can be connected in parallel to provide a current equal to the sum of the current limit settings.

Note that the output terminals are rated at 15A maximum; if two or more outputs are operated in parallel to source higher currents than this the junction should be made at a separate point, not one of the terminals.

Protection

Overvoltage protection (OVP) is fully variable within the range 10% to 110% of the supply's maximum output level. The OVP limit is set via the screwdriver adjustable SET OVP preset potentiometer, accessible through a hole in the front panel. Rotating the preset clockwise increases the limit, which can be read directly on the user display by pressing the button beneath the preset. If the voltage on the output exceeds the set OVP for any reason, including an externally forced voltage, the output will be tripped off.

The output will also be tripped off if an attempt is made to draw power from the sense wires.

When the output is tripped the OUTPUT lamp will still be ON but the displays will show ‘OP trip’ and the UNREG lamp will also light. Turn the output off; the trip message should be replaced with the normal preset V and I readings. When the cause of the trip has been removed the output can be switched on again.

10

Image 11
Contents XPF XPF Series Dual Output 35V 10A Powerflex DC Power SupplyContact Information Part NumberTable of Contents Output Specifications SpecificationMeter Specifications Safety Immunity EmissionsMounting InstallationMains Operating Voltage Mains LeadConnections Operation Protection Connection to the LoadRemote Sensing Series or Parallel connection with other unitsFuse MaintenanceCleaning VentilationEquipment Required Access to Calibration AdjustmentsCalibration OVP Calibration Set Power LimitVoltage Calibration Current CalibrationAVERTISSEMENT! CET Instrument Doit Etre Relie a LA Terre SécuritéMontage Tension d’utilisation secteurCâble secteur Opération ConnexionsConnexion en série ou en parallèle avec d’autres appareils Connexion à la chargeTélédétection Nettoyage FusibleWARNUNG! Dieses Gerät Muss Geerdet Werden SicherheitAufstellung/Montage NetzbetriebsspannungNetzkabel Betrieb AnschlüsseIstwert-Fernerfassung LeistungsgrenzeVerbraucheranschluss Überspannungsschutz Reihen- und Parallelschaltung mit anderen GerätenReinigung WartungSicherung Attenzione Questo Strumento Deve Essere Collegato a Terra SicurezzaMontaggio InstallazioneTensione d’esercizio Cavo d’AlimentazioneFunzionamento CollegamentoCollegamento in serie/parallelo con altre unità Limite di potenzaAllacciamento del carico Rilevamento a distanzaVentilazione ProtezionePulizia ManutenzioneFusibile ADVERTENCIA! Este Instrumento Debe Conectarse a Tierra SeguridadMontaje InstalaciónVoltaje de trabajo de alimentación Cable de redFuncionamiento ConexionesConexión en serie o en paralelo a otras unidades Conexión a la cargaDetector remoto Limpieza MantenimientoProtección VentilaciónHow do you get service? Warranty InformationProduct What does this warranty not cover?Return Material Authorization Policy Xantrex Technology Inc