Alphabetical reference |
| Commands and Queries Reference | |
RAMP? | return the current Ramp Duration for the Power Module. The result is | ||
| a string in the following format: m:ss:nnn where m=minutes, | ||
| ss=seconds and |
| |
| Syntax | RAMP? <ch> |
|
| Parameters | the number of the channel to be queried. | |
| Category | Settings | Type: Sequential |
RCL | restores settings of all the Power Modules. |
| |
| Syntax | RCL <int> |
|
| Parameters | a decimal number in the range 0 to 9 specifying the | |
|
| storage number the XMP 2600 will restore the | |
|
| settings from. |
|
| Category | System | Type: Overlapped |
RCL? | return an indication whether the Storage Area is free (result is “0”) or | ||
| not (result is “1”). |
| |
| Syntax | RCL? <int> |
|
| Parameters | a decimal number in the range 0 to 9 specifying the | |
|
| storage number to be checked. |
|
| Category | System | Type: Sequential. |
RESET | reset the entire XMP 2600 system: resets the Power Modules and the | ||
| Main Controller. |
|
|
| Syntax | RESET |
|
| Parameters | none |
|
| Category | System | Type: Sequential |
RIPL | program the Power Module to simulate ripple at its output. | ||
| Syntax | RIPL <ch>,<int>,<int> |
|
| Parameters | the number of the Power Module to be programmed. | |
|
| level of ripple: a decimal number in the range 0 to 2, | |
|
| selecting (respectively) one of the following levels: | |
|
| off, low, high. |
|
|
| frequency of ripple: a decimal number in the range 1 | |
|
| to 7, selecting (respectively) one of the following | |
|
| frequencies: |
|
|
| 1 = 50Hz |
|
|
| 2 = 60Hz |
|
|
| 3 = 100Hz |
|
|
| 4 = 120Hz |
|
|
| 5 = 400Hz |
|
|
| 6 = 800Hz |
|
|
| 7 = 2khz |
|
| Category | Settings | Type: Sequential |
58 | XMP 2600 Programming Manual rev. 1.1 |