Xantrex Technology PV-225208 Automatic State Transitions, Sleeping → Power Tracking → Sleeping

Page 22

SECTION 4

OPERATION

Figure 4-3

PV-225208 State Machine

• Power TrackingManual CurrentPower Tracking or Sleeping:

Verify the PV manual current parameter (I Manual %) is set to the desired percent of rated. Com- mand the PV-225208 to Manual Current mode from the operator interface keypad. While in the manual current mode, the user may change the PV manual current parameter. However, the user may demand greater current than the capacity of the PV array. If this causes the PV voltage to drop below the minimum operating voltage (330 Vdc), the PV-225208 will transition to Sleeping.

To exit the Manual Current mode the user must manually command the PV-225208 to either Power Tracking or Sleeping.

AUTOMATIC STATE TRANSITIONS

Sleeping Power Tracking Sleeping:

The On/Off switch must be turned to the On position. Once the PV voltage exceeds the PV voltage start setpoint (PV V Start) the PV-225208 will start a wake-up timer (PV T Start). If the PV voltage remains above the PV start voltage setpoint for the duration of the wake-up timer, the PV-225208 will transition to Power Tracking.

If the PV power drops below the PV power stop setpoint (PV P Stop) the PV-225208 will start a PV sleep timer (PV T Stop). If the PV voltage and power remain below their respective setpoints for the duration of the sleep timer, the PV-225208 will transition to Sleeping

DOCUMENT: 151811

PV-225208 Photovoltaic Inverter

4-6

 

Operation and Maintenance Manual

 

Copyright 2003, Xantrex Technology Inc.

Image 22
Contents Manual Table of Contents Major Components Operation and Maintenance ManualSection Product Description Introduction Main EnclosureSection Product Description Control ComponentsPower Control Unit PCU Interconnection Standards ComplianceSection Product Description Specifications Equipment SymbolFault Reporting Section Safety Safety FeaturesMain Enclosure Door Interlock Switch PV Ground Fault DetectionOver/Under Voltage and Frequency Section SafetyIsolation Procedure Anti Island ProtectionTorque and Wire Gauge Specifications Utility Side Isolation Transformer RequirementsInstallation Instructions Section Installation and Initial TURN-ONInstallation Cable Entry Area Array Grounding Interconnection Wiring Ground Fault DetectionInterface PV-225208 Inverter Wiring Diagram Chassis Gnd TransformerPV Array Frame Ground DC Interface Circuit BreakerVisual Inspection, Isolation Transformer WYE/WYE Visual Inspection, PV Array WiringInitial Power Visual Inspection, PV-225208System Verification Power Tracker Fine Tuning Overview Section Operation Description of System OperationOperating States Utility Voltage/Frequency Fault Automatic Reset Operation FeaturesFixed Unity Power Factor Operation Section OperationCurrent Imbalance Detection Peak Power TrackingOperator Interface DC Overvoltage DetectionSection Operation Manual State Transitions Commanding Goal State ChangesSetting the Date and Time Changing Write Parameter ValuesSleeping → Power Tracking → Sleeping Automatic State TransitionsTURN-ON Procedure AUTO-RESTART FeatureAny State → Fault Section Troubleshooting General Alarm and Fault ConditionsPV Overvoltage S Section TroubleshootingProgramming Mode S Bad Memory SAC Voltage Too Low S Door Interlock Switch Open HPV Auxiliary Switch Open H AC Voltage Too High SXX25/XX26 Line Gate Drive Fault S YY27/YY28 Line Over-Current Fault SPV Over-Current Fault S DC Bus Voltage High HSection Preventative Maintenance Periodic Maintenance Section Preventative Maintenance READ/WRITE Parameter Menu Section Appendix Faults CodesRead-Only Parameters Section Appendix Inverter StatesADC Warranty and Certification Drawings ListXantrex PV Series Limited Warranty and Registration Page Page Page Page Page Fab, Enclosure, Upper, 2 Bay, PV225208 Page Fab, Enclosure, DC Interface, PV225208 Page TB5 Source Control Specification