Xantrex Technology PV-225208 AUTO-RESTART Feature, TURN-ON Procedure, Any State → Fault

Page 23

SECTION 4

OPERATION

Any State Fault:

If the PV-225208 encounters a fault, regardless of operating state, it will transition to the Fault state. The PV-225208 will remain in this state until the fault condition has been remedied and cleared via the front panel.

A description of the fault will show on the first line of the operator interface LCD. The second line of the LCD will read ‘Clear Fault?’. To clear a fault press <ENTER>. The PV-225208 will transition to Sleeping. If the fault does not clear, the fault condition has not been corrected. If the ‘Clear Fault?’mes- sage is not shown on the second line of the LCD, scroll through the read parameter menu with the /\ or \/ keys until the message appears.

AUTO-RESTART FEATURE

In the event of a utility voltage or frequency surge or sag, which causes the inverter to shut down, the PV-225208 will automatically transition to a fault condition. Once the utility recovers for a period of five minutes, the PV-225208 will automatically clear the fault, then resume normal operation.

ISOLATION PROCEDURE

The following procedure should be followed to de-energize the PV-225208 for maintenance:

1.Turn the On/Off switch to the Off position.

2.Open the DC interface (PV array) disconnect switch.

3.Open theAC interface disconnect switch.

4.Open the isolation transformer circuit breaker.

5.Install lockout devices on the isolation transformer circuit breaker and PV disconnect switch.

WARNING

The terminals of the PV input may be energized if the arrays are energized. In addi- tion, allow 5 minutes for all capacitors within the main enclosure to discharge after disconnecting the PV-225208 fromAC and DC sources.

TURN-ON PROCEDURE

Refer to Section 3 for a detailed first-time turn on procedure.

1.Remove any lockout devices from the isolation transformer circuit breaker and PV disconnect switch.

2.Close the isolation transformer circuit breaker.

3.Close theAC interface disconnect switch.

4.Close DC interface (PV array) disconnect switch.

5.Turn the On/Off switch to the On position.

After a 15 second initialization period, the PV-225208 will automatically transition to ‘Waking Up’, given the PV voltage is greater than the PV V Start setpoint.

DOCUMENT: 151811

PV-225208 Photovoltaic Inverter

4-7

 

Operation and Maintenance Manual

 

Copyright 2003, Xantrex Technology Inc.

Image 23
Contents Manual Table of Contents Main Enclosure Operation and Maintenance ManualSection Product Description Introduction Major ComponentsControl Components Section Product DescriptionInterconnection Standards Compliance Power Control Unit PCUEquipment Symbol Section Product Description SpecificationsPV Ground Fault Detection Section Safety Safety FeaturesMain Enclosure Door Interlock Switch Fault ReportingAnti Island Protection Section SafetyIsolation Procedure Over/Under Voltage and FrequencyUtility Side Isolation Transformer Requirements Torque and Wire Gauge SpecificationsInstallation Section Installation and Initial TURN-ONInstallation Instructions Cable Entry Area Array Grounding Ground Fault Detection Interconnection WiringCircuit Breaker PV-225208 Inverter Wiring Diagram Chassis Gnd TransformerPV Array Frame Ground DC Interface InterfaceVisual Inspection, PV-225208 Visual Inspection, PV Array WiringInitial Power Visual Inspection, Isolation Transformer WYE/WYESystem Verification Power Tracker Fine Tuning Operating States Section Operation Description of System OperationOverview Section Operation Operation FeaturesFixed Unity Power Factor Operation Utility Voltage/Frequency Fault Automatic ResetDC Overvoltage Detection Peak Power TrackingOperator Interface Current Imbalance DetectionSection Operation Changing Write Parameter Values Commanding Goal State ChangesSetting the Date and Time Manual State TransitionsAutomatic State Transitions Sleeping → Power Tracking → SleepingAny State → Fault AUTO-RESTART FeatureTURN-ON Procedure Alarm and Fault Conditions Section Troubleshooting GeneralBad Memory S Section TroubleshootingProgramming Mode S PV Overvoltage SAC Voltage Too High S Door Interlock Switch Open HPV Auxiliary Switch Open H AC Voltage Too Low SYY27/YY28 Line Over-Current Fault S XX25/XX26 Line Gate Drive Fault SDC Bus Voltage High H PV Over-Current Fault SSection Preventative Maintenance Periodic Maintenance Section Preventative Maintenance Read-Only Parameters Section Appendix Faults CodesREAD/WRITE Parameter Menu Inverter States Section AppendixADC Drawings List Warranty and CertificationXantrex PV Series Limited Warranty and Registration Page Page Page Page Page Fab, Enclosure, Upper, 2 Bay, PV225208 Page Fab, Enclosure, DC Interface, PV225208 Page TB5 Source Control Specification