Xantrex Technology PV-225208 PV Over-Current Fault S, DC Bus Voltage High H

Page 28

SECTION 5

TROUBLESHOOTING

Pins 1 and 3 are correct, the CT may be damaged.

Clear the fault and restart the PCU. If the fault is sustained contact your Xantrex Technology distributor for assistance or service.

0828 – PV Over-Current Fault (S)

Current through the PV CT has exceeded the allowable limit.

Possible causes:

PV system wiring short: Inspect the PV power system for short circuits.

PCU Power Supply is defective: Verify +/-15Vdc sources, referenced to analog ground, on the

PCU. There are labeled test points on the PCU circuit board. Note: There are two isolated +15Vdc power supplies labeled +15Vdc and +15Vdc Drv. The +15Vdc Drv power supply provides power for the matrix driver boards only.

Faulty CT wiring: Verify the wiring between the PCU and the CT is properly connected and undam- aged. Refer to the system schematic in Section 7.

CT defective: Locate the current transducer for the PV leg in question (see control components drawing in Section 7). With a digital multi-meter measure the voltage from CT pins 1, 2, and 3 to chassis ground. Pins 1 and 3 should read approximately +15 and -15Vdc respectively. These volt- ages are sourced directly from the PCU. Pin 2 should read less than 20mV when no current is passing through the CT window. If Pin 2 reads greater than 20mV, and the supply voltages are on Pins 1 and 3 are correct, the CT may be damaged

Clear the fault and restart the PCU. If the fault is sustained contact your Xantrex Technology distributor for assistance or service.

8021 - DC Bus Voltage High (H)

The DC Bus voltage has exceeded the maximum allowable limit.

This fault is generally transient in nature. Clear the fault and attempt to restart the PV-225208.

DOCUMENT: 151811

PV-225208 Photovoltaic Inverter

5-5

 

Operation and Maintenance Manual

 

Copyright 2003, Xantrex Technology Inc.

Image 28
Contents Manual Table of Contents Operation and Maintenance Manual Section Product Description IntroductionMajor Components Main EnclosureSection Product Description Control ComponentsPower Control Unit PCU Interconnection Standards ComplianceSection Product Description Specifications Equipment SymbolSection Safety Safety Features Main Enclosure Door Interlock SwitchFault Reporting PV Ground Fault DetectionSection Safety Isolation ProcedureOver/Under Voltage and Frequency Anti Island ProtectionTorque and Wire Gauge Specifications Utility Side Isolation Transformer RequirementsInstallation Instructions Section Installation and Initial TURN-ONInstallation Cable Entry Area Array Grounding Interconnection Wiring Ground Fault DetectionPV-225208 Inverter Wiring Diagram Chassis Gnd Transformer PV Array Frame Ground DC InterfaceInterface Circuit BreakerVisual Inspection, PV Array Wiring Initial PowerVisual Inspection, Isolation Transformer WYE/WYE Visual Inspection, PV-225208System Verification Power Tracker Fine Tuning Overview Section Operation Description of System OperationOperating States Operation Features Fixed Unity Power Factor OperationUtility Voltage/Frequency Fault Automatic Reset Section OperationPeak Power Tracking Operator InterfaceCurrent Imbalance Detection DC Overvoltage DetectionSection Operation Commanding Goal State Changes Setting the Date and TimeManual State Transitions Changing Write Parameter ValuesSleeping → Power Tracking → Sleeping Automatic State TransitionsTURN-ON Procedure AUTO-RESTART FeatureAny State → Fault Section Troubleshooting General Alarm and Fault ConditionsSection Troubleshooting Programming Mode SPV Overvoltage S Bad Memory SDoor Interlock Switch Open H PV Auxiliary Switch Open HAC Voltage Too Low S AC Voltage Too High SXX25/XX26 Line Gate Drive Fault S YY27/YY28 Line Over-Current Fault SPV Over-Current Fault S DC Bus Voltage High HSection Preventative Maintenance Periodic Maintenance Section Preventative Maintenance READ/WRITE Parameter Menu Section Appendix Faults CodesRead-Only Parameters Section Appendix Inverter StatesADC Warranty and Certification Drawings ListXantrex PV Series Limited Warranty and Registration Page Page Page Page Page Fab, Enclosure, Upper, 2 Bay, PV225208 Page Fab, Enclosure, DC Interface, PV225208 Page TB5 Source Control Specification