Xantrex Technology PV-225208 AC Voltage Too Low S, AC Voltage Too High S

Page 26

SECTION 5

TROUBLESHOOTING

0063 - AC Voltage Too Low (S)

TheAC Inverter voltage fell below the minimum programmed limit (MinAC Volt).

This problem was caused by the utility. Clear the fault and restart the PV-225208.

Possible causes:

High momentary load which forces the inverter to current limit

Fuses F1, F2, F3, F4, F5 or F6 blown

SSR-1 inoperable

Contactor K1 inoperable

Utility voltage fell below the allowable limit.

This fault is self-clearing. Once the utility voltage has recovered within the acceptable operating range, the PV-225208 will automatically clear this fault and resume normal operation after 5 minutes. If the fault will not clear, verify the adjustable setpoint is below the actual utility voltage. If the fault is sustained, contact your Xantrex Technology distributor for assistance or service.

0064 - AC Voltage Too High (S)

The inverter controller voltage exceeded the maximum-programmed limit (Max AC Volt).

Possible causes:

SSR-1 inoperable

Contactor K1 inoperable

Utility voltage exceeded the allowable limit.

This fault is self-clearing. Once the utility voltage has recovered within the acceptable operating range, the PV-225208 will automatically clear this fault and resume normal operation after 5 minutes. If the fault will not clear, verify the adjustable setpoint is above the actual utility voltage. If the fault is sustained, contact your Xantrex Technology distributor for assistance or service.

012A - Interrupt Time-Out (S)

The PCU was not able to service the interrupt for approximately 1 second.

Attempt to clear the fault and restart the PV-225208 by pressing the black reset button on the lower left corner of the PCU. If the fault is sustained, replacement or service of the PCU will be necessary.

0230 – Door Interlock Switch Open (H)

The door interlock lock switch located in the inside upper left corner of the main enclosure door is open.

If the switch is closed and the fault still registers on the front panel, isolate the PV-225208 from external power, then:

Verify continuity across the switch contact block while the switch is closed.

Verify continuity between PCU-J2-5 and PCU-J3-3.

0430 - PV Auxiliary Switch Open (H)

DOCUMENT: 151811

PV-225208 Photovoltaic Inverter

5-3

 

Operation and Maintenance Manual

 

Copyright 2003, Xantrex Technology Inc.

Image 26
Contents Manual Table of Contents Major Components Operation and Maintenance ManualSection Product Description Introduction Main EnclosureSection Product Description Control ComponentsPower Control Unit PCU Interconnection Standards ComplianceSection Product Description Specifications Equipment SymbolFault Reporting Section Safety Safety FeaturesMain Enclosure Door Interlock Switch PV Ground Fault DetectionOver/Under Voltage and Frequency Section SafetyIsolation Procedure Anti Island ProtectionTorque and Wire Gauge Specifications Utility Side Isolation Transformer RequirementsInstallation Section Installation and Initial TURN-ONInstallation Instructions Cable Entry Area Array Grounding Interconnection Wiring Ground Fault DetectionInterface PV-225208 Inverter Wiring Diagram Chassis Gnd TransformerPV Array Frame Ground DC Interface Circuit BreakerVisual Inspection, Isolation Transformer WYE/WYE Visual Inspection, PV Array WiringInitial Power Visual Inspection, PV-225208System Verification Power Tracker Fine Tuning Operating States Section Operation Description of System OperationOverview Utility Voltage/Frequency Fault Automatic Reset Operation FeaturesFixed Unity Power Factor Operation Section OperationCurrent Imbalance Detection Peak Power TrackingOperator Interface DC Overvoltage DetectionSection Operation Manual State Transitions Commanding Goal State ChangesSetting the Date and Time Changing Write Parameter ValuesSleeping → Power Tracking → Sleeping Automatic State TransitionsAny State → Fault AUTO-RESTART FeatureTURN-ON Procedure Section Troubleshooting General Alarm and Fault ConditionsPV Overvoltage S Section TroubleshootingProgramming Mode S Bad Memory SAC Voltage Too Low S Door Interlock Switch Open HPV Auxiliary Switch Open H AC Voltage Too High SXX25/XX26 Line Gate Drive Fault S YY27/YY28 Line Over-Current Fault SPV Over-Current Fault S DC Bus Voltage High HSection Preventative Maintenance Periodic Maintenance Section Preventative Maintenance Read-Only Parameters Section Appendix Faults CodesREAD/WRITE Parameter Menu Section Appendix Inverter StatesADC Warranty and Certification Drawings ListXantrex PV Series Limited Warranty and Registration Page Page Page Page Page Fab, Enclosure, Upper, 2 Bay, PV225208 Page Fab, Enclosure, DC Interface, PV225208 Page TB5 Source Control Specification