Xantrex Technology PV-225208 important safety instructions XX25/XX26 Line Gate Drive Fault S

Page 27

SECTION 5

TROUBLESHOOTING

The dry contact auxiliary switch mounted to the PV disconnect switch has been toggled. The auxiliary switch should be opened when the PV disconnect switch is open. If the fault will not clear when the PV disconnect switch is closed:

Isolate PV-225208 from utility power.

Close PV disconnect switch and check continuity between PCU J3-3 and PCU J2-7. If there is no continuity, inspect wiring between the PCU and the auxiliary switch (see page 2 of the system schematic for further detail).

XX25/XX26 - Line Gate Drive Fault (S)

One of the IGBT gate drive boards signaled the PCU that there was a fault. The second two digits refer to which matrix has the fault. XX25 refers to matrix 1 and XX26 refers to matrix 2. The particular device at which the fault was detected is indicated by the first two digits of the fault code, as follows:

XX: 01 = Phase A+

02 = Phase A-

04 = Phase B+

08 = Phase B-

10 = Phase C+

20 = Phase C-

If more than one phase faults simultaneously, the error code will contain the summation of phase fault values. For example, if phaseA+ and B+ of matrix 1 fault simultaneously, the error will read 0525.

Make sure the fiber optics for the device and matrix in question are properly connected to the driver board. Similarly, make sure the fiber is properly connected at the PCU.

Clear the fault and restart the PV-225208. If the fault is sustained, contact your Xantrex Technology distributor for assistance or service.

YY27/YY28 - Line Over-Current Fault (S)

Current in one phase of the matrix has exceeded the allowable limit. YY27 refers to matrix 1 and YY28 refers to matrix2. The faulted phase is indicated by the first two digits of the fault code, as follows:

YY:01 = Phase A

02 = Phase B

04 = Phase C

If more than one phase faults simultaneously, the error code will contain the summation of phase fault values. For example, if phaseAand C of matrix 1 fault simultaneously, the error will read 0527.

Possible causes:

AC system wiring short: Inspect the AC power system for short circuits.

PCU Power Supply is defective: Verify +/-15Vdc sources, referenced to analog ground, on the

PCU. There are labeled test points on the PCU circuit board. Note: There are two isolated +15Vdc power supplies labeled +15Vdc and +15Vdc Drv. The +15Vdc Drv power supply provides power for the matrix driver boards only.

Faulty CT wiring: Verify the wiring between the PCU power supply and the CT is properly con- nected and undamaged. Refer to page 2 of the system schematic in Section 7.

CT defective: Locate the current transducer for the matrix and phase in question (see control com- ponents drawing in Section 7). With a digital multi-meter measure the voltage from CT pins 1, 2, and 3 to chassis ground. Pins 1 and 3 should read approximately +15 and -15Vdc respectively. These voltages are sourced directly from the PCU. Pin 2 should read less than 20mV when no current is passing through the CT window. If Pin 2 reads greater than 20mV, and the supply voltages are on

DOCUMENT: 151811

PV-225208 Photovoltaic Inverter

5-4

 

Operation and Maintenance Manual

 

Copyright 2003, Xantrex Technology Inc.

Image 27
Contents Manual Table of Contents Main Enclosure Operation and Maintenance ManualSection Product Description Introduction Major ComponentsControl Components Section Product DescriptionInterconnection Standards Compliance Power Control Unit PCUEquipment Symbol Section Product Description SpecificationsPV Ground Fault Detection Section Safety Safety FeaturesMain Enclosure Door Interlock Switch Fault ReportingAnti Island Protection Section SafetyIsolation Procedure Over/Under Voltage and FrequencyUtility Side Isolation Transformer Requirements Torque and Wire Gauge SpecificationsSection Installation and Initial TURN-ON Installation InstructionsInstallation Cable Entry Area Array Grounding Ground Fault Detection Interconnection WiringCircuit Breaker PV-225208 Inverter Wiring Diagram Chassis Gnd TransformerPV Array Frame Ground DC Interface InterfaceVisual Inspection, PV-225208 Visual Inspection, PV Array WiringInitial Power Visual Inspection, Isolation Transformer WYE/WYESystem Verification Power Tracker Fine Tuning Section Operation Description of System Operation OverviewOperating States Section Operation Operation FeaturesFixed Unity Power Factor Operation Utility Voltage/Frequency Fault Automatic ResetDC Overvoltage Detection Peak Power TrackingOperator Interface Current Imbalance DetectionSection Operation Changing Write Parameter Values Commanding Goal State ChangesSetting the Date and Time Manual State TransitionsAutomatic State Transitions Sleeping → Power Tracking → SleepingAUTO-RESTART Feature TURN-ON ProcedureAny State → Fault Alarm and Fault Conditions Section Troubleshooting GeneralBad Memory S Section TroubleshootingProgramming Mode S PV Overvoltage SAC Voltage Too High S Door Interlock Switch Open HPV Auxiliary Switch Open H AC Voltage Too Low SYY27/YY28 Line Over-Current Fault S XX25/XX26 Line Gate Drive Fault SDC Bus Voltage High H PV Over-Current Fault SSection Preventative Maintenance Periodic Maintenance Section Preventative Maintenance Section Appendix Faults Codes READ/WRITE Parameter MenuRead-Only Parameters Inverter States Section AppendixADC Drawings List Warranty and CertificationXantrex PV Series Limited Warranty and Registration Page Page Page Page Page Fab, Enclosure, Upper, 2 Bay, PV225208 Page Fab, Enclosure, DC Interface, PV225208 Page TB5 Source Control Specification