SECTION 6

PREVENTATIVE MAINTENANCE

Mechanical electrical connections will loosen over time. This is caused primarily by thermal cycling during normal operation.As connections loosen, electrical impedance will increase at the connection, eventually leading to fire and component damage. It is critical to check all electrical connections every six months.

Inductor Enclosure

Access the inductor enclosure and remove any accumulated dirt and debris. Vacuum enclosure whenever dust or dirt is present.

ISOLATION PROCEDURE

The following procedure should be followed to de-energize the PV-225208 for maintenance:

WARNING

The terminals of the PV input may be energized if the arrays are energized. In addition, allow 5 minutes for all capacitors within the enclosure to discharge af- ter shutting down the PV-225208.

1.Turn the on/off switch to the off position.

2.Open the DC interface (PV array) disconnect switch.

3.Open the AC interface disconnect switch.

4.Open the isolation transformer circuit breaker.

5.Install lockout devices on the isolation transformer circuit breaker and PV disconnect switch.

TURN-ON PROCEDURE

Refer to Section 3 for a detailed first-time turn on procedure.

1.Remove any lockout devices from the isolation transformer circuit breaker and PV disconnect switch.

2.Close the isolation transformer circuit breaker.

3.Close the AC interface disconnect switch.

4.Close the DC interface (PV array) disconnect switch.

5.Turn the on/off switch to the on position.

After a 15 second initialization period and a 5 minute wake up period, the PV-225208 will automatically begin power tracking, given the PV voltage is greater than the PV start voltage setpoint.

DOCUMENT: 151811

PV-225208 Photovoltaic Inverter

6-2

 

Operation and Maintenance Manual

 

Copyright 2003, Xantrex Technology Inc.

Image 30
Contents Manual Table of Contents Major Components Operation and Maintenance ManualSection Product Description Introduction Main EnclosureSection Product Description Control ComponentsPower Control Unit PCU Interconnection Standards ComplianceSection Product Description Specifications Equipment SymbolFault Reporting Section Safety Safety FeaturesMain Enclosure Door Interlock Switch PV Ground Fault DetectionOver/Under Voltage and Frequency Section SafetyIsolation Procedure Anti Island ProtectionTorque and Wire Gauge Specifications Utility Side Isolation Transformer RequirementsSection Installation and Initial TURN-ON Installation InstructionsInstallation Cable Entry Area Array Grounding Interconnection Wiring Ground Fault DetectionInterface PV-225208 Inverter Wiring Diagram Chassis Gnd TransformerPV Array Frame Ground DC Interface Circuit BreakerVisual Inspection, Isolation Transformer WYE/WYE Visual Inspection, PV Array WiringInitial Power Visual Inspection, PV-225208System Verification Power Tracker Fine Tuning Section Operation Description of System Operation OverviewOperating States Utility Voltage/Frequency Fault Automatic Reset Operation FeaturesFixed Unity Power Factor Operation Section OperationCurrent Imbalance Detection Peak Power TrackingOperator Interface DC Overvoltage DetectionSection Operation Manual State Transitions Commanding Goal State ChangesSetting the Date and Time Changing Write Parameter ValuesSleeping → Power Tracking → Sleeping Automatic State TransitionsAUTO-RESTART Feature TURN-ON ProcedureAny State → Fault Section Troubleshooting General Alarm and Fault ConditionsPV Overvoltage S Section TroubleshootingProgramming Mode S Bad Memory SAC Voltage Too Low S Door Interlock Switch Open HPV Auxiliary Switch Open H AC Voltage Too High SXX25/XX26 Line Gate Drive Fault S YY27/YY28 Line Over-Current Fault SPV Over-Current Fault S DC Bus Voltage High HSection Preventative Maintenance Periodic Maintenance Section Preventative Maintenance Section Appendix Faults Codes READ/WRITE Parameter MenuRead-Only Parameters Section Appendix Inverter StatesADC Warranty and Certification Drawings ListXantrex PV Series Limited Warranty and Registration Page Page Page Page Page Fab, Enclosure, Upper, 2 Bay, PV225208 Page Fab, Enclosure, DC Interface, PV225208 Page TB5 Source Control Specification