Xantrex Technology PV-225208 important safety instructions Torque and Wire Gauge Specifications

Page 9

SECTION 3

INSTALLATION AND INITIAL TURN-ON

ISOLATION TRANSFORMER REQUIREMENTS

The PV-225208 UL1741 certification requires the use of a Xantrex Technology specified 225 kVA WYE/ WYE isolation transformer between the inverter AC output and the utility interconnection (See Appendix in Section 7 for transformer dimensions and specifications. This custom 225 kVA isolation transformer is not part of the 225 kVA inverter, but can be ordered as a separate item. If maintaining the listing to UL1741 is not a requirement for your application, contact Xantrex Technology for a fact sheet describing the installation op- tions and precautions for installing this inverter in a photovoltaic system that does not require UL1741 compli- ance.

WARNING

Xantrex Technology requires installing an isolation transformer between the PV- 225208 inverter and the point of utility interconnection. Failure to do so could result in catastrophic damage to the PV-225208 as well as the utility distribution system and will void the product warranty.

Inverter Side Isolation Transformer Requirements

The inverter side of the isolation transformer is configured as a WYE, and is rated for 208 VAC. The neutral (X0) connection on the inverter side must be left floating. If the neutral is tied to ground, the inverter will be damaged internally at power-up.

Utility Side Isolation Transformer Requirements

The utility side windings of the isolation transformer are configured WYE, and must match the voltage at the utility inter-tie. Verify that the transformer supplied matches the voltage requirement. Also, the transformer is supplied with a neutral connection on the utility side. Connection of this utility-side neutral does not affect the operation of the inverter. Check local jurisdiction for their requirements regarding the connection of this neutral.

Contact your Xantrex Technology distributor if you have any questions regarding isolation transformer requirements.

TORQUE AND WIRE GAUGE SPECIFICATIONS

The following torque specifications are to be used on all electrical interfaces made during installation of the PV-225208.

Torque Table

Terminal Block or Bolt Size

Torque Setting

 

 

3/8-16 Bolt (AC)

250 in lbs./28.2 Nm

 

 

Terminal Block (DC+, DC-,

275 in lbs/31.1 Nm

& DC Neutral)

 

 

 

DOCUMENT: 151811

PV-225208 Photovoltaic Inverter

3-1

 

Operation and Maintenance Manual

Copyright 2003, Xantrex Technology Inc.

Image 9
Contents Manual Table of Contents Section Product Description Introduction Operation and Maintenance ManualMajor Components Main EnclosureControl Components Section Product DescriptionInterconnection Standards Compliance Power Control Unit PCUEquipment Symbol Section Product Description SpecificationsMain Enclosure Door Interlock Switch Section Safety Safety FeaturesFault Reporting PV Ground Fault DetectionIsolation Procedure Section SafetyOver/Under Voltage and Frequency Anti Island ProtectionUtility Side Isolation Transformer Requirements Torque and Wire Gauge SpecificationsSection Installation and Initial TURN-ON Installation InstructionsInstallation Cable Entry Area Array Grounding Ground Fault Detection Interconnection WiringPV Array Frame Ground DC Interface PV-225208 Inverter Wiring Diagram Chassis Gnd TransformerInterface Circuit BreakerInitial Power Visual Inspection, PV Array WiringVisual Inspection, Isolation Transformer WYE/WYE Visual Inspection, PV-225208System Verification Power Tracker Fine Tuning Section Operation Description of System Operation OverviewOperating States Fixed Unity Power Factor Operation Operation FeaturesUtility Voltage/Frequency Fault Automatic Reset Section OperationOperator Interface Peak Power TrackingCurrent Imbalance Detection DC Overvoltage DetectionSection Operation Setting the Date and Time Commanding Goal State ChangesManual State Transitions Changing Write Parameter ValuesAutomatic State Transitions Sleeping → Power Tracking → SleepingAUTO-RESTART Feature TURN-ON ProcedureAny State → Fault Alarm and Fault Conditions Section Troubleshooting GeneralProgramming Mode S Section TroubleshootingPV Overvoltage S Bad Memory SPV Auxiliary Switch Open H Door Interlock Switch Open HAC Voltage Too Low S AC Voltage Too High SYY27/YY28 Line Over-Current Fault S XX25/XX26 Line Gate Drive Fault SDC Bus Voltage High H PV Over-Current Fault SSection Preventative Maintenance Periodic Maintenance Section Preventative Maintenance Section Appendix Faults Codes READ/WRITE Parameter MenuRead-Only Parameters Inverter States Section AppendixADC Drawings List Warranty and CertificationXantrex PV Series Limited Warranty and Registration Page Page Page Page Page Fab, Enclosure, Upper, 2 Bay, PV225208 Page Fab, Enclosure, DC Interface, PV225208 Page TB5 Source Control Specification