Xantrex Technology PV-225208 Section Troubleshooting, PV Overvoltage S, Programming Mode S

Page 25

SECTION 5

TROUBLESHOOTING

Possible causes:

Inspect the PV array for ground faults.

CT8 defective: Troubleshoot the ground fault CT8, located on the power distribution panel of the main enclosure (see system schematic drawing in Section 7), using the procedures described in fault YY27.

0032 - PV Overvoltage (S)

The PV voltage has exceeded the maximum programmed limit (PV Max Volt).

Check the PV input voltage at the PV disconnect switch. If the voltage is below 600 VDC, clear the alarm and restart the PV-225208.

0040 - In Programming Mode (S)

System is in reload PROM mode.

0042 - Bad Memory (S)

The static memory test failed upon system initialization. This fault is generally transient in nature.

Attempt to clear the fault by either cycling control power or pressing the black reset button in the lower left corner of the PCU. If the fault is sustained, replacement or service of the PCU will be necessary.

0045 – Line Matrix Failure to Turn On (S)

0046 – Line Matrix Failure to Turn Off (S)

Software was not able turn on or turn off the indicated switching matrix.

Attempt to clear the fault by either cycling control power or pressing the black reset button in the lower left corner of the PCU. If the fault is sustained, replacement or service of the PCU will be necessary.

0061 – Line AC Frequency Too Low (S)

The AC line frequency fell below the allowable limit.

This fault is self-clearing. Once the utility frequency has recovered within the acceptable operating range, the PV-225208 will automatically clear this fault and resume normal operation after 5 minutes. If the fault will not clear, verify the adjustable setpoint is below the actual utility frequency. If the fault is sustained, contact your Xantrex Technology distributor for assistance or service.

0062 - Line AC Frequency Too High (S) The AC frequency exceeded the allowable limit.

This fault is self-clearing. Once the utility frequency has recovered within the acceptable operating range, the PV-225208 will automatically clear this fault and resume normal operation after 5 minutes. If the fault will not clear, verify the adjustable setpoint is above the actual utility frequency. If the fault is sustained, contact your Xantrex Technology distributor for assistance or service.

DOCUMENT: 151811

PV-225208 Photovoltaic Inverter

5-2

 

Operation and Maintenance Manual

 

Copyright 2003, Xantrex Technology Inc.

Image 25
Contents Manual Table of Contents Section Product Description Introduction Operation and Maintenance ManualMajor Components Main EnclosureControl Components Section Product DescriptionInterconnection Standards Compliance Power Control Unit PCUEquipment Symbol Section Product Description SpecificationsMain Enclosure Door Interlock Switch Section Safety Safety FeaturesFault Reporting PV Ground Fault DetectionIsolation Procedure Section SafetyOver/Under Voltage and Frequency Anti Island ProtectionUtility Side Isolation Transformer Requirements Torque and Wire Gauge SpecificationsInstallation Instructions Section Installation and Initial TURN-ONInstallation Cable Entry Area Array Grounding Ground Fault Detection Interconnection WiringPV Array Frame Ground DC Interface PV-225208 Inverter Wiring Diagram Chassis Gnd TransformerInterface Circuit BreakerInitial Power Visual Inspection, PV Array WiringVisual Inspection, Isolation Transformer WYE/WYE Visual Inspection, PV-225208System Verification Power Tracker Fine Tuning Overview Section Operation Description of System OperationOperating States Fixed Unity Power Factor Operation Operation FeaturesUtility Voltage/Frequency Fault Automatic Reset Section OperationOperator Interface Peak Power TrackingCurrent Imbalance Detection DC Overvoltage DetectionSection Operation Setting the Date and Time Commanding Goal State ChangesManual State Transitions Changing Write Parameter ValuesAutomatic State Transitions Sleeping → Power Tracking → SleepingTURN-ON Procedure AUTO-RESTART FeatureAny State → Fault Alarm and Fault Conditions Section Troubleshooting GeneralProgramming Mode S Section TroubleshootingPV Overvoltage S Bad Memory SPV Auxiliary Switch Open H Door Interlock Switch Open HAC Voltage Too Low S AC Voltage Too High SYY27/YY28 Line Over-Current Fault S XX25/XX26 Line Gate Drive Fault SDC Bus Voltage High H PV Over-Current Fault SSection Preventative Maintenance Periodic Maintenance Section Preventative Maintenance READ/WRITE Parameter Menu Section Appendix Faults CodesRead-Only Parameters Inverter States Section AppendixADC Drawings List Warranty and CertificationXantrex PV Series Limited Warranty and Registration Page Page Page Page Page Fab, Enclosure, Upper, 2 Bay, PV225208 Page Fab, Enclosure, DC Interface, PV225208 Page TB5 Source Control Specification