Xantrex Technology RS232-XHR manual Remote/Local Operation on

Page 50

Operation

Command Reference

Command

Description

OUT <1/ON>,<0/OFF>

Enables or disables the supply’s voltage/current output. The supply will

 

continue to accept new commands while the output is disabled but these

 

will not be implemented until OUT ON or OUT 1 is received. OUT ON is the

 

default setting. When you start the supply in remote mode, the output is

 

enabled.

 

OUT OFF (or OUT 0) also sets the isolation signal on the rear panel J7

 

connector, line 3. You can use the to trip external relays to isolate the power

 

supply from the load.

 

Initial value: OUT ON (or OUT 1) for output enabled

 

 

OUT?

Asks for the present enabled/disabled status of the supply’s output

 

voltage/current.

 

Response: OUT 1 output enabled or

 

OUT 0 output disabled

OVCAL

Causes the master controller to perform automatic calibration of the

 

supply’s over voltage protection circuitry. Set CMODE ON before using this

 

command. Ensure jumper J65 on the RS-232 Interface PCB is connected

 

for remote operation.

OVSET <voltage>

Sets the supply’s over voltage protection trip point in volts (default) or in

 

millivolts. If the trip point is exceeded, or if the trip point value is lower than

 

the present output voltage setting, the supply will ignore the command, turn

 

on the ERR LED, and set the ERR bit in the accumulated status register.

 

Reset with the RST command.

 

Range: 0 to 110% of model maximum output voltage (VMAX)

 

Initial value: 110% of model VMAX

 

 

OVSET?

Asks for the supply’s present over voltage protection limit.

 

Response: OVSET <voltage>

REN <1/ON>,<0/OFF>

Remote Enable. When set to REN 0, the power supply is in local mode. If a

 

command is sent from the computer, the power supply does not respond

 

but remains in local mode. When set to REN 1, the power supply will enter

 

remote mode if a command is sent from the computer. See also

 

“Remote/Local Operation” on page 27.

REN?

Asks for the state of the remote enable. See REN command.

 

Response: REN <state>

 

 

ROM?

Asks for the version number of the master and slave EPROMs located on

 

the interface PCB.

 

Response: ROM M:<version> S:<version>

 

 

RST

Resets the supply to present voltage and current settings if the output is

 

disabled by over voltage or foldback protection. Output values may be

 

changed via VSET, ISET, and OVSET while the unit is disabled, but those

 

values will not take effect until RST is applied.

48

Operating Manual for RS-232 for XHR/XFR Series Power Supply

Image 50
Contents RS232-XHR RS232-XFR Page Operating Manual for How do you get service? Phone 604 422 Toll Free North America 800 667 Fax 604 421What does this warranty not cover? Disclaimer Product Information About Your Power Supply Model Number Serial Number Purchased From Purchase DateSafety SupplyMain Sections Manual RevisionsAbout This Manual Contents Calibration Features and Specifications DescriptionFeatures and Specifications Features and FunctionsFeatures Readback FunctionsSpecifications Models 140 12-100 20-60 35-35 40-30Models 60-20 100-12 150-8 300-4 600-2 Models 300 12-220 20-130 33-85 40-70 Models 60-46 100-28 150-18 300-9 600-4 Models 130 20-50 33-33 40-25 60-18 Models 100-10 150-7 300-3.5 600-1.7 Introduction Initial InspectionInstallation and Configuration Initial InspectionRS-232 Interface Subplate Located on Power Supply Rear Panel RS-232 Interface PCB Basic Setup Procedure Step # Description Action ReferenceBaud Rate Flow Switch Setting ConditionCommunications XON Switch Setting Condition Jumper Connections RS-232 Connector PinPower Supply DCE Host Computer DTE Pin connector Jumper J216 Connections RS-232 Connector PinStartup Switch Position Power on resultsRemote Condition Default Settings Model Example IsetExample Local Lockout CommandRS-232 Connection Power Supply Settings Parameter SettingUser Options and Settings 12 OVP Control Mode SelectionHigh OFF LOW User Signals User Signals J7 ConnectorJ7 User Signal Connector Circuit Block Diagram J7 User Cable with Ferrite Block Command Syntax RS-232 OperationOperation FormatParameter Description Form Floating Number Definition ExampleOperation Command Summary Command DescriptionAUXA? Cmode Command Reference Auxa 1 onResponse DLY seconds Lockout. See also Remote/Local Operation on Snsp Remote/Local Operation on Status, and Fault Registers on Section Accumulated Status, Status, and Fault Registers Condition Mnemonic Bit Position Bit Weight 4096Error Codes Error # Error Identification ExplanationTroubleshooting LEDsCalibration Voltage Program Calibration Procedure Voltage Mode CalibrationSetup VoltageVoltage Readback Calibration Procedure Current Program Calibration Procedure Current Mode CalibrationCurrent Calibration Setup Current Readback Calibration Procedure Over Voltage Protection OVP Calibration Page Xantrex Technology Inc