Compaq 3000 Series manual Removing the connector block

Page 28

2-6Compaq 3000 Series UPS Operation and Reference Guide

Use this procedure to activate the REPO port:

1.Install a suitable switch at the required remote location.

2.Remove the connector block from the REPO port.

REMOTE

POWER OFF

Figure 2-2. Removing the connector block

3.Wire the connector block using stranded, non-shielded wire (AWG #22 - #18, or equivalent).

4.Replace the connector block in the REPO port.

REMOTE

POWER OFF

Figure 2-3. Replacing the connector block

IMPORTANT: The remote switch must be in the OFF (open) position to enable power to the output receptacles.

Image 28 Contents
3000SeriesUPS Page Contents Installation Iv Compaq 3000 Series UPS Operation and Reference GuideAppendix a Appendix C Vi Compaq 3000 Series UPS Operation and Reference GuideAbout This Guide Text ConventionsSymbols on Equipment Symbols in TextViii Compaq 3000 Series UPS Operation and Reference Guide Precautions About This GuideGetting Help Rack StabilityCompaq 3000 Series UPS Operation and Reference Guide Compaq Technical Support Compaq Website Compaq Authorized ResellerOverview Compaq 3000 Series UPS Models Front PanelsSeries UPS Models 2Compaq 3000 Series UPS Operation and Reference GuideRear Panels Overview4Compaq 3000 Series UPS Operation and Reference Guide Communications port Standard UPS Features 6Compaq 3000 Series UPS Operation and Reference GuidePower Management Software Communications PortHardware Option Cards Compaq Power Management Software8Compaq 3000 Series UPS Operation and Reference Guide Compaq Multi-Server UPS Card Compaq Scalable UPS CardCompaq SNMP-EN Internal Adapter Remote Emergency Power Off Repo Port10Compaq 3000 Series UPS Operation and Reference Guide Pre-Failure Battery Warranty $25,000 Computer Load Protection GuaranteeWarranties Installation Items not supplied with the UPS kit Installation RequirementsItems supplied with the UPS kit Installation Before Starting the UPSRack Mounting the UPS Connecting to the Communications Port Connecting the Remote Emergency Power OffRemoving the connector block Checking the Battery Recharge Date Label Starting the UPSConnecting the UPS to Utility Power Connecting Devices to the UPSPowering up the UPS Front panel LED display and controlsCompleting the Installation Check the front panel LED displayPlacing the UPS in Operate mode Installation is Now CompleteOperation Standby Mode Operate ModeConfigure Mode Modes of OperationFront Panel Controls Sleep ModeOperation 4Compaq 3000 Series UPS Operation and Reference Guide Front Panel LEDs Standby and Operate Modes Front Panel IndicatorsAC Input LEDs Battery Charge LEDs Site Wiring Fault LEDBattery Service LED Communication LED Load Level LEDsOn LED Overcurrent Protection Overcurrent ProtectionPlacing the UPS in Operate Mode Returning to Standby Mode Standby mode controlsInitiating a Self-test Audio Alarm Silencing an Audio AlarmAudio Alarm Conditions 12Compaq 3000 Series UPS Operation and Reference GuideOperation Configuration Placing the UPS in Configure Mode Configure mode controls On LED LED On buttonConfiguration Parameters and their LED Indicators ConfigurationConfiguration Parameters/LED Indicators ExplanationConfiguration Parameters/LED Indicators Changing Configuration Parameters Optimizing Battery Life By Matching the Utility Voltage Nominal Configuration Operating Ranges VAC North America and Japanese Models Operating Ranges VAC All High Voltage ModelsBattery Maintenance 2Compaq 3000 Series Operation and Reference Guide Battery Maintenance When to Replace BatteriesCharging Batteries Pre-Failure Battery Warranty Obtaining New BatteriesReplacing Batteries 4Compaq 3000 Series Operation and Reference GuideRemoving the Battery Pack To replace batteries with the UPS Operate mode hot-swappingPreparing the UPS To replace batteries with the UPS Off6Compaq 3000 Series Operation and Reference Guide Removing the faceplateRemove two screws to access the battery pack Disconnecting the battery pack terminal connections 8Compaq 3000 Series Operation and Reference GuideInstalling New Batteries Sliding the battery pack out to reveal the second handleReplacing the battery cable retainer bracket Battery cables 10Compaq 3000 Series Operation and Reference GuideTesting New Batteries Disposing of Used Batteries Care and Storage of Batteries12Compaq 3000 Series Operation and Reference Guide Troubleshooting Troubleshooting During Start Troubleshooting Guide UPS StartTroubleshooting Guide After Start Troubleshooting After StartTroubleshooting Troubleshooting Guide After Start Repairing the UPS Regulatory Compliance Notices Federal Communications Commission NoticeClass a Equipment Class B EquipmentCables ModificationsRegulatory Compliance Notices A-3 Canadian Notice Avis Canadien European Union NoticeJapanese Notice Taiwanese Notice Regulatory Compliance Notices A-5Battery Replacement Notice Electrostatic Discharge Grounding Methods Specifications Physical Specifications Input SpecificationsTable C-1 Physical Specifications 3000 Series UPS Models Table C-2 Input Specifications 3000 Series UPS ModelsTable C-3 Output Specifications 3000 Series UPS Models Output SpecificationsSpecifications C-3 Table C-4 Output Specifications 3000 Series UPS Models OutputBattery Specifications Table C-6 Battery Specifications 3000 Series UPS ModelsSpecifications C-5 Table C-5 Overcurrent Protection Per ModelBattery Runtime Environmental Specifications Specifications C-7Numbers and Symbols IndexCompaq 3000 Series UPS Operation and Reference Guide Index Http Index Important Safety Information Important Safety Information x, 2-2,2-3 Compaq 3000 Series UPS Operation and Reference Guide
Related manuals
Manual 24 pages 45.81 Kb