4-4 Compaq 3000 Series UPS Operation and Reference Guide
Table 
Configuration Parameters/LED Indicators
| Parameter | 
 | Parameter | 
 | LED 16 | 
 | Explanation | 
| (LED) | 
 | Name | 
 | Status | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 1 | 
 | 120/230 Nom | 
 | On1 | 
 | Nominal utility voltage level is | 
| 
 | 
 | 
 | 
 | 
 | 
 | 120/230 VAC. | 
| 
 | 
 | 
 | 
 | 
 | 
 | (Default for R3000, R3000h, | 
| 
 | 
 | 
 | 
 | 
 | 
 | and  | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 2 | 
 | 110/220 Nom | 
 | On1 | 
 | Nominal utility voltage level is | 
| 
 | 
 | 
 | 
 | 
 | 
 | 110/220 VAC. | 
| 3 | 127/240 Nom | On1 | 
| 
 | 
 | 
 | 
| 10 | 100/208 Nom | On1 | 
Nominal utility voltage level is 127/240 VAC.
Nominal utility voltage level is 100/208 VAC.
(Default for R3000j and 
| 4 | Extended | On | UPS will supply utility power if the utility | 
| 
 | Voltage | 
 | voltage is within +20% to  | 
| 
 | 
 | 
 | nominal voltage. If the utility voltage is | 
| 
 | 
 | 
 | outside this range, the UPS will supply | 
battery power.
(This option not available on the R3000j and 
Off
(default)
UPS will supply utility power if the utility voltage is within ±20% of the nominal voltage. If the utility voltage is outside this range, the UPS will supply battery power.
| 5 | Wiring | On | Enables an audio alarm if ground is | 
| 
 | Fault | (default) | missing, or if line and neutral connections | 
| 
 | 
 | 
 | have been reversed. | 
| 
 | 
 | 
 | (This option not available on the R3000j | 
| 
 | 
 | 
 | and  | 
| 
 | 
 | 
 | 
 | 
| 
 | 
 | Off | Disables the audio alarm for this event. | 
| 
 | 
 | 
 | (Default for R3000j and  | 
| 
 | 
 | 
 | 
 | 
| 6 | Low | On | Enables an audio alarm 3 minutes before | 
| 
 | Battery | (default) | battery shutdown. | 
| 
 | 
 | 
 | 
 | 
| 
 | 
 | Off | Enables an audio alarm 5 minutes before | 
| 
 | 
 | 
 | battery shutdown. | 
continued