 | Troubleshooting  | |
| Table  | 
 | 
 | 
 | 
 | 
 | 
| Troubleshooting Guide (After Start) continued | 
 | 
 | 
 | ||
| Symptom | 
 | Possible Cause | 
 | Suggested Action | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
| LED 10 is red | 
 | Potential battery failure detected | 
 | Allow batteries to charge for 24 | |
| (Battery | 
 | 
 | 
 | hours, then initiate  | |
| Service) | 
 | 
 | 
 | LED 10 is red, replace batteries. | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | New batteries improperly | 
 | Check connections. | |
| 
 | 
 | connected | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
| LED 10 is | 
 | Internal UPS overvoltage condition | 
 | Shut down the UPS. Contact an | |
| flashing red; | 
 | exists | 
 | authorized service provider. | |
| audio alarm | 
 | 
 | 
 | 
 | 
 | 
| cannot be | 
 | 
 | 
 | 
 | 
 | 
| silenced | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
Repairing the UPS
Repairs to the UPS must be carried out by Compaq or a Compaq Authorized Service Provider. Other than battery replacement, there are no