C-6 Compaq 3000 Series UPS Operation and Reference Guide
Battery Runtime
|
|
| Table |
| Estimated Battery Runtime | ||
|
|
|
|
Load (VA) |
|
| Battery Runtime (Minutes) |
700 | 80 | ||
|
|
| |
800 | 56 | ||
|
| ||
900 | 50 | ||
|
| ||
1000 | 45 | ||
|
| ||
1200 | 38 | ||
|
| ||
1400 | 32 | ||
|
| ||
1500 | 30 | ||
|
| ||
1800 | 21 | ||
|
| ||
2000 | 19 | ||
|
| ||
2200 | 17 | ||
|
| ||
2400 | 14 | ||
|
| ||
3000 | 11 | ||
|
|
|
|
If a device list the power in Watts, use the following conversion equation:
Volts x Amps = VA per device
If only Watts are given:
Watts x 1.35 = VA
VA/1000 = KVA