4-10 Compaq 3000 Series UPS Operation and Reference Guide
Table 
Operating Ranges (VAC) – North America and Japanese Models
| Nominal Level | 
 | Normal Range | 
 | Extended Range | 
| 100 | 
 | 80 to 120 | 
 | Not applicable for R3000j | 
| 
 | 
 | 
 | 
 | 
 | 
| 110 | 
 | 88 to 132 | 
 | 72 to 132 | 
| 
 | 
 | 
 | 
 | 
 | 
| 120 | 
 | 96 to 144 | 
 | 78 to 144 | 
| 
 | 
 | 
 | 
 | 
 | 
| 127 | 
 | 102 to 152 | 
 | 83 to 155 | 
| 
 | 
 | 
 | 
 | 
 | 
Table 
Operating Ranges (VAC) – All High Voltage Models
| Nominal Level | 
 | Normal Range | 
 | Extended Range | 
| 208 | 
 | 166 to 250 | 
 | Not applicable for | 
| 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
| 220 | 
 | 176 to 264 | 
 | 143 to 264 | 
| 
 | 
 | 
 | 
 | 
 | 
| 230 | 
 | 184 to 276 | 
 | 150 to 276 | 
| 
 | 
 | 
 | 
 | 
 | 
| 240 | 
 | 192 to 288 | 
 | 156 to 288 | 
| 
 | 
 | 
 | 
 | 
 | 
3.For nominal voltage level setting, select configuration parameters 1, 2, 3, or 10 (see Table 
4.Access parameter 4 to switch from normal to extended range (see Table