3-6 Compaq 3000 Series UPS Operation and Reference Guide
Site Wiring Fault (LED 5)
| 
 | 
 | 
 | 
 | Table  | 
| 
 | 
 | 
 | 
 | Site Wiring Fault LED | 
| 
 | 
 | 
 | 
 | 
 | 
| LED | 
 | Color | 
 | Meaning | 
| 
 | 
 | 
 | 
 | 
 | 
| 5 | 
 | Red | 
 | No ground connection between utility power and the UPS. | 
| 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | The line and neutral connections between utility power and the | 
| 
 | 
 | 
 | 
 | UPS are reversed. | 
| 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | The UPS voltage configuration may be incorrect. | 
| 
 | 
 | 
 | 
 | 
 | 
Note: For units 
Battery Charge (LEDs 6-9) 
| 
 | 
 | 
 | 
 | Table  | 
| 
 | 
 | 
 | 
 | Battery Charge LEDs | 
| 
 | 
 | 
 | 
 | 
 | 
| LED | 
 | Color | 
 | Meaning | 
| 
 | 
 | 
 | 
 | 
 | 
| 6 | 
 | Green | 
 | Batteries are between 67% and 100% charged. | 
| 
 | 
 | 
 | 
 | (LEDs 7 and 8 are also green) | 
| 
 | 
 | 
 | 
 | 
 | 
| 7 | 
 | Green | 
 | Batteries are approximately 66% charged. | 
| 
 | 
 | 
 | 
 | (LED 8 is also green) | 
| 
 | 
 | 
 | 
 | 
 | 
| 8 | 
 | Green | 
 | Batteries are approximately 33% charged. | 
| 
 | 
 | 
 | 
 | 
 | 
| 9 | 
 | Red | 
 | Batteries are low; approximately three to five minutes of battery | 
| 
 | 
 | 
 | 
 | backup remain. | 
| 
 | 
 | 
 | 
 | 
 | 
Battery Service (LED 10)
| 
 | 
 | 
 | 
 | Table  | 
| 
 | 
 | 
 | 
 | Battery Service LED | 
| 
 | 
 | 
 | 
 | 
 | 
| LED | 
 | Color | 
 | Meaning | 
| 
 | 
 | 
 | 
 | 
 | 
| 10 | 
 | Red | 
 | Potential battery failure. | 
| 
 | 
 | 
 | 
 | 
 | 
Note: When LED 10 is red, the audio alarm will sound, indicating the UPS has detected a potential battery failure. The UPS batteries may need to be replaced in 30 to 60 days.