AMD 1207 manual Thermal Solution Design Requirements, Sample Heat Sinks and Attachment Methods

Page 16

Thermal Design Guide for Socket F (1207) Processors

32800 Rev. 3.02 August 2006

Depending on the system features and layout, more space around the socket may be available for the thermal solution than is shown in Figure 2 on page 15. This space permits heat sink designs with better thermal performance.

Appendix A on page 37 shows a complete, detailed set of keep-out drawings for the AMD PIB thermal solution for socket F (1207).

3.2Thermal Solution Design Requirements

Table 2 provides the design-target specifications that must be met for the processor to operate reliably in a typical platform using the AMD PIB thermal solution for socket F (1207) processors.

Table 2. Thermal Solution Design Requirements for Platforms Using Socket F (1207) PIB processors

Symbol

Description

Maximum

 

 

 

L

Length of heat sink

68 mm

 

 

 

W

Width of heat sink

77 mm

 

 

 

H

Height of heat sink

60 mm

 

 

 

θca

Case-to-ambient thermal

0.26°C/W1

 

resistance

 

MHS

Mass of heat sink

450 g to 700 g2

Fclip

Clip force

75 lbs ±15 lbs

TA

Local ambient temperature near

38°C

 

processor

 

 

 

 

Notes:

1. This is the thermal resistance required for dual-core, 90-nm socket F (1207) processors. The thermal resistance requirement may vary depending on the product OPN. The user should consult the processor data sheet for the thermal requirements specific to the part.

2. Heat sinks weighing up to 450 g can be attached to the motherboard. Heat sinks weighing over 450 g should be tied directly to the chassis for reliable shock and vibration performance.

3.3Sample Heat Sinks and Attachment Methods

The heat sink, fan, mounting spring clip, and thermal interface material used for the AMD PIB thermal solution for socket F (1207) processors are the same as the heat sink, fan, mounting spring clip, and thermal interface material used for systems based on the socket 940 processor.

The backplate and retention frame are different from those used in the socket 940 processor. The EMC shield implemented in the socket 940-based systems is not recommended for AMD PIB thermal solutions for socket F (1207) processors.

16

Thermal Design of Platforms Using the AMD Processor-In-a-

Chapter 3

 

Box (PIB) Thermal Solution

 

Image 16
Contents Thermal Design Guide for Socket F 1207 Processors Advanced Micro Devices, Inc. All rights reserved Contents Heat Sink Fans Thermal Interface Material List of Figures List of FiguresList of Figures List of Tables List of TablesList of Tables Revision History Revision HistoryRevision History Summary of Requirements Chapter IntroductionChapter Processor Specifications Chapter Processor Thermal SolutionsSocket Description 1207-Pin SocketMotherboard Component Height Restrictions Thermal Solution Design Requirements Sample Heat Sinks and Attachment MethodsPart Description Material Quantity Backplate Assembly Retention Frame Thermal Design of Platforms Using the AMD Processor-In-a Thermal Design of Custom 1U-2P Systems Chapter Thermal Design of Custom 1U-2P SystemsSymbol Systems Exploded View of Thermal Solution for Custom 1U-2P Systems Spring ScrewsHeat Sink Fin ParametersFans Thermal Interface Material Thermal Design of Custom 1U-2P Systems Thermal Design of Custom 2U-4P Systems Chapter Thermal Design of Custom 2U-4P SystemsThermal Solution Design Requirements Heat sink Aluminum Fan Plastic Spring clip Backplate Assembly Spring Clip Chemical Element of SK7 Spring SteelHigh Performance Heat Sink for Custom 2U-4P Systems Fans Thermal Design of Custom 2U-4P Systems Solution for Socket F 1207 Processors Appendix aSocket F 1207 PIB Board Component Height Restrictions 787 64.36 76.41 49.91 59.81Socket F 1207 PIB Socket Outline and Socket Window 724 000 784 520 1891207 PIB Heat Sink Height Zone2x11.44 2x51.26 2x61.08 36.59 32.13 27.59Keep-Out 1207 PIB318 000 885 233 Thermal10.09 33.91 49.91 Solution for Socket F 1207 Processors Appendix B Socket F 1207 ProcessorDrawings for 12072P Systems Processor Height RestrictionsBased Holes, Contact Pads,No-Routing Zone 32.16 71.98 24.54 10.09 49.91 64.36Based on ProcessorWindow Height Restriction Zone 1U-2P Systems 1207 Processor42.71 82.53 32.16 71.98 Keep-Out 2P Board No-Through-Hole KeepOut 598 000 166 40.59 80.411207 1U 233 335 96535.04 22.04 10.09 33.9 49.91 61.86Socket F 1207 Processor Appendix C Socket F 1207 2U-4P Board Component Height Restrictions 4P Mounting Holes, Contact Pads, and No-Routing Zone 47.40 87.22 35.6524.54 64.36 75.471207 2U-4P Socket Outline Custom 2U-4PSocket Window 2U-4P Systems 1207 Processor 17.59260 681 266Socket F 1207 2U-4P Board No-Through-Hole Keep-Out 40.59 80.411207 166 80.41Socket F 1207 Processor Appendix D Socket F 1207 ProcessorsStreamline Plot of AMD Reference Custom 2U-4P System