APC ACRC103, ACRC100 manual Positioning the Equipment, Service access, Leveling

Page 20

Positioning the Equipment

Service access

An area of 1143 mm (45 in) of clear floor space in front and

914.4 mm (36 in) in back of the equipment is required for service. All required maintenance can be performed from the front or back of the equipment.

na1565a

Dimensions are shown in mm (in).

Leveling

The leveling feet provide a stable base if the floor is uneven, but cannot compensate for a badly sloped surface.

Once the equipment is in its intended location, use a screwdriver to turn each leveling foot until it makes contact with the floor. Adjust each foot until the equipment is level and plumb.

You can remove the casters and leveling feet to allow the

na1572a

equipment to rest directly on the floor.

 

14

InRow RC Installation

Image 20
Contents Installation 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Mechanical Connections Overview SafetyManual updates Cross-reference symbol used in this manual Damage to Equipment or Personnel Installation kit Inspecting the EquipmentInventory Door and side panel locksComponent Identification ExteriorInterior User interface connection panel Incoming power supply requirements Room PreparationPiping Diagrams With cooling distribution unit CDUWithout CDU Top piping InRow Bottom piping To customer Supplied chillerInternal piping diagram Out From Coils FullFull Bypass OpenPiping and electrical access locations Dimensions are shown in mmWeights and Dimensions Removing Doors and Panels Door removal Side panel removalLeveling Service accessPositioning the Equipment Joining to enclosures Stabilizing the EquipmentFloor brackets Mechanical Connections PipingConnect piping Condensate pump drain connection Accessories and spare parts ChillerFilling and Purging Than 76 l/m 20 gpm Electrical Connections Power connections User interface connection pinout Control ModbusLink ports Network port Control connector ModbusForm C alarm contacts and shutdown input Leak detector portTemperature sensor APC Worldwide Customer Support 990-2402D-001 11/2012