Form C alarm contacts and shutdown input

Remote switch using internal power (24 Vdc shown)

Field-supplied voltage (12/24 Vdc or Vac)

A relay internal to the user interface is typically controlled by a user-defined alarm (malfunctioning fans, for example). Before an alarm is detected, the voltage on the COM terminal is routed to the NC terminal. When the alarm is activated, the relay is energized, causing the voltage on the COM terminal to be routed to the NO terminal. The NO and NC terminals may be connected to remote indicator lights, a warning buzzer, or another device to alert an operator to the presence of an alarm condition.

A remote disconnect switch may be connected to the shutdown inputs.

Leak detector port

Rope water detector (AP9325). Up to four optional rope water detectors can be installed in series. The rope water detector connects to the RJ-45 leak detector port located at the top of the interface box.

See the “Rope Water Detector” installation sheet

(supplied with the kit) for installation and setup information.

na1584a

28

InRow RC Installation

Image 34
Contents Installation 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Mechanical Connections Manual updates Cross-reference symbol used in this manual SafetyOverview Damage to Equipment or Personnel Inventory Installation kitInspecting the Equipment Door and side panel locksComponent Identification ExteriorInterior User interface connection panel Incoming power supply requirements Room PreparationPiping Diagrams With cooling distribution unit CDUWithout CDU Top piping InRow Bottom piping To customer Supplied chillerInternal piping diagram Out From Coils FullFull Bypass OpenPiping and electrical access locations Dimensions are shown in mmWeights and Dimensions Removing Doors and Panels Door removal Side panel removalPositioning the Equipment Service accessLeveling Floor brackets Stabilizing the EquipmentJoining to enclosures Mechanical Connections PipingConnect piping Condensate pump drain connection Accessories and spare parts ChillerFilling and Purging Than 76 l/m 20 gpm Electrical Connections Power connections User interface connection pinout Control ModbusLink ports Network port Control connector ModbusForm C alarm contacts and shutdown input Leak detector portTemperature sensor APC Worldwide Customer Support 990-2402D-001 11/2012