Electrical Connections

The following electrical connections are required in the field:

Feeds A and B

A-Link

Network Management Card

Temperature sensor

Communication (building management system)

See the electrical schematic (located on the lid of the electrical box) for all electrical connections.

Make all electrical connections in accordance with national and local codes.

See the InRow RC nameplate for voltage and current requirements.

A power disconnect is required to isolate each InRow RC for maintenance and service.

All low-voltage connections, including data and control connections, must be made with properly insulated wires. The low-voltage connections must have 300-V minimum insulation.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Turn off all power supplying this equipment before working on the equipment.

Use a voltmeter to ensure that power is turned off before making any electrical connections.

Failure to follow these instructions will result in death or serious injury.

Note: Single phase service is required. Electrical service must conform to national and local electrical codes. The InRow RC is grounded through the power cord.

22

InRow RC Installation

Image 28
Contents Installation 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Mechanical Connections Manual updates Cross-reference symbol used in this manual SafetyOverview Damage to Equipment or Personnel Installation kit Inspecting the EquipmentInventory Door and side panel locksComponent Identification ExteriorInterior User interface connection panel Incoming power supply requirements Room PreparationPiping Diagrams With cooling distribution unit CDUWithout CDU Top piping InRow Bottom piping To customer Supplied chillerInternal piping diagram Out From Coils FullFull Bypass OpenPiping and electrical access locations Dimensions are shown in mmWeights and Dimensions Removing Doors and Panels Door removal Side panel removalPositioning the Equipment Service accessLeveling Floor brackets Stabilizing the EquipmentJoining to enclosures Mechanical Connections PipingConnect piping Condensate pump drain connection Accessories and spare parts ChillerFilling and Purging Than 76 l/m 20 gpm Electrical Connections Power connections User interface connection pinout Control ModbusLink ports Network port Control connector ModbusForm C alarm contacts and shutdown input Leak detector portTemperature sensor APC Worldwide Customer Support 990-2402D-001 11/2012