Room Preparation
During the design of the data center, consider ease of entry for the equipment, floor loading factors, and accessibility to piping and wiring.
Seal the room with a vapor barrier to minimize moisture infiltration. (Polyethylene film is recommended for ceiling and wall applications.) Apply rubber- or
Insulate the room to minimize the influence of exterior heat loads. Use the minimum required amount of fresh air for make up to comply with local and national codes and regulations. Fresh air imposes extreme load variation on the cooling equipment from summer to winter and causes increased operating costs.
The equipment is designed as a sensible cooling air conditioning unit for
Note: The InRow RC is not intended to be used in an occupied office environment, due to potentially high noise levels during peak loads. Install the InRow RC in a computer room where people are normally present only for maintenance.
Incoming power supply requirements
See the electrical rating label on the equipment to determine the maximum possible current draw of the equipment. Provide either a single outlet circuit or a Power Distribution Unit (PDU) with sufficient capacity to handle all loads. Do not plug two InRow RC units into the same branch circuit or PDU.
The equipment must be grounded. Electrical service must conform to national and local electrical codes and regulations.
InRow RC Installation | 7 |