APC ACRC100, ACRC103 manual Room Preparation, Incoming power supply requirements

Page 13

Room Preparation

During the design of the data center, consider ease of entry for the equipment, floor loading factors, and accessibility to piping and wiring.

Seal the room with a vapor barrier to minimize moisture infiltration. (Polyethylene film is recommended for ceiling and wall applications.) Apply rubber- or plastic-based paints to concrete walls and floors.

Insulate the room to minimize the influence of exterior heat loads. Use the minimum required amount of fresh air for make up to comply with local and national codes and regulations. Fresh air imposes extreme load variation on the cooling equipment from summer to winter and causes increased operating costs.

The equipment is designed as a sensible cooling air conditioning unit for in-row use in data centers. The equipment does not have humidification or dehumidification control. Room humidity must be within acceptable operating conditions before starting equipment. If operated in spaces where the humidity is in the unacceptable operating conditions section of the Operating Guidelines chart (see the InRow RC Operation and Maintenance manual) the equipment condenses excess water vapor from the air. This will exceed the pumping capacity of the condensate pump, causing the equipment to send an alarm and shut down to avoid overflowing the condensate pan. The condensate pump runs until the fluid level in the pan is reduced, and the alarm is automatically reset. The equipment self-regulates in this manner until normal operating conditions are present.

Note: The InRow RC is not intended to be used in an occupied office environment, due to potentially high noise levels during peak loads. Install the InRow RC in a computer room where people are normally present only for maintenance.

Incoming power supply requirements

See the electrical rating label on the equipment to determine the maximum possible current draw of the equipment. Provide either a single outlet circuit or a Power Distribution Unit (PDU) with sufficient capacity to handle all loads. Do not plug two InRow RC units into the same branch circuit or PDU.

The equipment must be grounded. Electrical service must conform to national and local electrical codes and regulations.

InRow RC Installation

7

Image 13
Contents Installation 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Mechanical Connections Manual updates Cross-reference symbol used in this manual SafetyOverview Damage to Equipment or Personnel Inspecting the Equipment Installation kitInventory Door and side panel locks Exterior Component IdentificationInterior User interface connection panel Room Preparation Incoming power supply requirementsWith cooling distribution unit CDU Piping DiagramsTop piping InRow Bottom piping To customer Supplied chiller Without CDUOut From Coils FullFull Bypass Open Internal piping diagramDimensions are shown in mm Piping and electrical access locationsWeights and Dimensions Door removal Side panel removal Removing Doors and PanelsPositioning the Equipment Service accessLeveling Floor brackets Stabilizing the EquipmentJoining to enclosures Piping Mechanical ConnectionsConnect piping Condensate pump drain connection Chiller Accessories and spare partsFilling and Purging Than 76 l/m 20 gpm Electrical Connections Power connections Control Modbus User interface connection pinoutLink ports Network port Modbus Control connectorLeak detector port Form C alarm contacts and shutdown inputTemperature sensor 990-2402D-001 11/2012 APC Worldwide Customer Support