Page 24

Condensate pump. The pump is factory-wired and piped internally to the lower condensate pan. The pump is capable of moving liquid a maximum of 15.2 m (50 ft), including a maximum lift of 4.9 m (16 ft). For example, if your lift is 3 m (10 ft), you have 12.2 m (40 ft) of usable run. The pump also uses an on-board condensate high level float switch, which is wired into the InRow RC alarm input for local and remote alarm capabilities.

na1575a

CAUTION

CONDENSATE DAMAGE

Do not exceed the lift or the run length of the drain system.

To prevent equipment damage from condensate, do not leave the condensate drain line coiled inside the equipment. Route the condensate drain line out the top or bottom of the equipment before operation.

Failure to follow these instructions can result in equipment damage.

Condensate pump drain connection.

Note: Sufficient PVC drain line is

supplied to route the drain to the Condensate drain line outside of the equipment. To route the drain line to a remote drain,

obtain additional hardware.

na2271a

18

InRow RC Installation

Image 24
Contents Installation 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Mechanical Connections Safety Manual updates Cross-reference symbol used in this manualOverview Damage to Equipment or Personnel Installation kit Inspecting the EquipmentInventory Door and side panel locksComponent Identification ExteriorInterior User interface connection panel Incoming power supply requirements Room PreparationPiping Diagrams With cooling distribution unit CDUWithout CDU Top piping InRow Bottom piping To customer Supplied chillerInternal piping diagram Out From Coils FullFull Bypass OpenPiping and electrical access locations Dimensions are shown in mmWeights and Dimensions Removing Doors and Panels Door removal Side panel removalService access Positioning the EquipmentLeveling Stabilizing the Equipment Floor bracketsJoining to enclosures Mechanical Connections PipingConnect piping Condensate pump drain connection Accessories and spare parts ChillerFilling and Purging Than 76 l/m 20 gpm Electrical Connections Power connections User interface connection pinout Control ModbusLink ports Network port Control connector ModbusForm C alarm contacts and shutdown input Leak detector portTemperature sensor APC Worldwide Customer Support 990-2402D-001 11/2012