Mechanical Connections

Piping

Note: Ensure coolant water quality complies with guidelines set forth in IB0125GB001.

Water. Install shutoff valves for routine service and emergency isolation of the equipment. When a CDU is not used, you must install circuit setters to regulate the chilled water flow for each InRow RC air conditioner. See “Piping Diagrams,” beginning on page 8.

Layout and piping considerations.

Fluid pipes are not allowed directly above electrical equipment. All piping must be installed above the aisles as shown. If any piping makes a turn, or must be routed over electrical equipment, there must be a drip tray under the pipe that will protect the equipment from condensation and leaks. All piping must be kept separate from any electrical runs or wiring.

Hot Aisle Containment

CDU

Top piping examples shown

 

NetShelter NetShelter NetShelter

UPS

PDU

NetShelter RC NetShelter NetShelter RC NetShelter

InRow

PDU

UPS NetShelter RC NetShelter NetShelter RC NetShelter

CDU

NetShelter NetShelter RC NetShelter NetShelter RC NetShelter NetShelter

na1941a

Insulation. Insulate water lines to protect

personnel and to minimize condensation.

Note: Using either tape or glue, completely seal the insulation boots covering the unused supply and return connections.

16

InRow RC Installation

Image 22
Contents Installation 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Mechanical Connections Manual updates Cross-reference symbol used in this manual SafetyOverview Damage to Equipment or Personnel Inventory Installation kitInspecting the Equipment Door and side panel locksComponent Identification ExteriorInterior User interface connection panel Incoming power supply requirements Room PreparationPiping Diagrams With cooling distribution unit CDUWithout CDU Top piping InRow Bottom piping To customer Supplied chillerInternal piping diagram Out From Coils FullFull Bypass OpenPiping and electrical access locations Dimensions are shown in mmWeights and Dimensions Removing Doors and Panels Door removal Side panel removalPositioning the Equipment Service accessLeveling Floor brackets Stabilizing the EquipmentJoining to enclosures Mechanical Connections PipingConnect piping Condensate pump drain connection Accessories and spare parts ChillerFilling and Purging Than 76 l/m 20 gpm Electrical Connections Power connections User interface connection pinout Control ModbusLink ports Network port Control connector ModbusForm C alarm contacts and shutdown input Leak detector portTemperature sensor APC Worldwide Customer Support 990-2402D-001 11/2012