INSTALLATION
Hardwired UPS Installation
W A R N I N G
Only qualified service personnel (such as a licensed electrician) shall perform the electrical installation. Risk of electrical shock.
C A U T I O N
SFor UPS models with hardwired outputs, overcurrent protection for the output AC circuit(s) is to be provided by others.
SFor UPS models with hardwired outputs, suitably rated disconnect switches for the output AC circuit(s) are to be provided by others.
NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damage may occur to your equipment and void your warranty.
The Powerware 9125 hardwired models require a dedicated branch circuit that meets the following requirements:
S16A,
SThe protection device requires a
SThe breaker must be
SFor Europe, the breaker must be approved by the appropriate safety agency (such as TÜV or VDE) and have a contact air gap of at least 3 mm
S
S
S50/60 Hz
SFlexible metal conduit (recommended for ease of service and maintenance)
EATON Powerware® 9125 | 27 |