Powerware 2500 manual How to Replace Extended Battery Modules

Page 61

UPS MAINTENANCE

How to Replace Extended Battery Modules

C A U T I O N

The Extended Battery Module (EBM) is heavy (see page 61). A minimum of two people are required to lift the EBM when it is replaced.

To replace the Extended Battery Modules (EBMs):

1.Unplug the EBM cable from the UPS.

NOTE For 230V models, remove the fixed cover plate, and then unplug the EBM cable from the UPS.

If additional EBMs are installed, unplug the EBM cable from the battery connector on each EBM.

2.If the EBM is in a tower configuration, remove the joining brackets.

3.If the EBM has pedestals installed, remove the pedestals and retain.

4.If the EBM is in a rack, install the mounting handles and brackets on the new EBM.

5.Replace the EBM. See “Recycling the Used Battery or UPS” on page 57 for proper disposal.

6.Reinstall the pedestals if removed in Step 3.

7.Reinstall the joining brackets if removed in Step 2.

8.Plug the EBM cable(s) into the battery connectors as shown in Figure 45.

For E/EH UPS models, remove the cover from the EBM cable and plug the EBM cable into the UPS. Attach the fixed cover plate to the EBM cable.

9.For additional EBMs, plug the EBM cable into the battery connector on the adjacent EBM.

For E/EH UPS models, remove the EBM battery connector cover. Remove the cover from the EBM cable of the second cabinet and plug the EBM cable into the battery connector on the first EBM.

Attach the fixed cover plate to the EBM cable.

EATON Powerware® 9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D

55

www.powerware.com

 

Image 61 Contents
Powerware 9125 Two-in-One UPS 2500/3000 VA User’s Guide FCC Part ICES-003 Class a EMC StatementsRequesting a Declaration of Conformity Special Symbols Table of Contents Specifications Troubleshooting UPS MaintenanceWarranty Chapter Introduction Introduction R N I N G N G E RSikkerhedsanvisninger U T I O NR E Belangrijke Veiligheidsinstructies V a R S E LV a a R A R S C H U W I N GTarkeita Turvaohjeita G E L E TA R a R O I T U SN G E R Consignes de sécuritéR N U N G SicherheitswarnungenH T U N G R I C O L O Avvisi di sicurezzaV E R T E N Z a Viktig Sikkerhetsinformasion T E N Z I O N ER L I G R S I K T I GI D a D O Regulamentos de SegurançaV E R T Ê N C I a R I G OПредупреждения по мерам безопасности L I G R O Advertencias de SeguridadV E R T E N C I a E C a U C I Ó NR a SäkerhetsföreskrifterK T I G T Inspecting the Equipment Chapter InstallationUPS Setup Connecting the UPS Internal BatteryRack-Mount Setup Tower Setup Installing UPS Pedestals for One Cabinet Installing EBM Pedestals Tower Setup with Three Cabinets Typical EBM Installation 120V UPS Model Shown Extended Battery Module InstallationRemove the cover from the EBM cable as shown in Figure EBM Installation for E/EH UPS Models Only Typical Installation 120V UPS Model Shown Plug-Receptacle UPS InstallationFault Indicators Hardwired UPS Installation Typical Hardwired UPS Installation Function Position EUH Models UPS Wire FunctionSize Rating Torque Fault Indicators Remote Emergency Power-off Installation Repo Connector 3000 VA, 120V Rear Panel UPS Rear Panels3000 VA, 208-240V Hardwired Rear Panel Turning the UPS On Starting the UPS on BatteryInitiating the Self-Test Turning the UPS OffUPS Front Panel Operating ModesNormal Mode Battery Mode Bypass Mode Chapter Configuration Using Configuration Mode Configuration Mode Option LED Status Explanation LEDs Configuration Mode LEDs and OptionsConfiguration Slot Cards Additional UPS FeaturesSingle-Port Card Communication Port Pin Assignment Signal Name FunctionOn-Bypass Relay Jumper Network Transient Protector Network Transient ProtectorUPS Load Segments for 120V Models Load Segments Storing the UPS and Batteries UPS and Battery CareReplacing Batteries When to Replace BatteriesHow to Replace UPS Internal Batteries Slide the new battery trays into the UPS How to Replace Extended Battery Modules EBM Connections 120V UPS Model Shown Testing New BatteriesRecycling the Used Battery or UPS UPS Maintenance Model Number Power Levels Nominal Voltage Input Voltage Model SpecificationsTechnical Specifications Power ConnectionsEnvironmental and Safety Weights and DimensionsBattery Runtimes in Minutes at Full/Half Load BatteryAlarm Indicators Audible Alarms and UPS ConditionsAlarm or Condition Possible Cause Action Troubleshooting GuideShutdown Low Battery Alarm or Condition Possible Cause Action Shutdown imminentService and Support Two-Year Limited Warranty US and Canada WarrantyWarranty Ten-Year Pro-Rated Limited Warranty US and Canada Warranty Load Protection Guarantee US and Canada Warranty