Liebert XDK user manual Condensed Water Connection, Preparations for Connecting, Rear, Front

Page 18

Installation and Commissioning

Figure 10 Bottom plate with cutouts

Sealed Cable Cutout

Network

Cable

Entry

Rear

Cutout for

Water Pipes

Condensed

Water Cutouts

Front

Cable and pipe openings must be sealed air-tight on completion of work.

5.4Condensed Water Connection

If the XDK is operated below dew point, condensed water may occur. As standard there is a water con- nection, 5/8" diameter, in the condensed water tray for drainage.

Preparations for Connecting

Step 1): Remove the air duct

Condensate connection

Step 2): Remove the cap

Step 3.) Connect the nipple with a drain hose 5/8"

Step 4.)

Move and snap the nipple with hose into the hole

When connecting to the condensate tray, ensure that the condensed water pipe is connected to a self- filling siphon with return protection and that the condensate drain is properly sloped.

The height of the siphon must be designed for an underpressure or overpressure of 0.11psi (800 Pa) so that air is not drawn into or blown out of the waste pipe.

14

Image 18
Contents UserManual-17kW Important Safety Instructions Table of Contents Figures Introduction Proper Application Operating ConditionsGeneral operating data General function DescriptionPrinciple of Cooling Operation Air / WaterHeat Exchanger Technical data Data Overview-XDKXDK general data Control Automatic Door OpeningFunction Initial CommissioningManual Closing Manual OpeningPackaging Material HandlingEquipment INSPECTION, Handling and Storage Storage Returning the Unit in Case of DamagePositioning the XDK Preparation for InstallationInstallation and Commissioning Remove Recirculation Air Duct Transport LockWater Connection Preparing Heat Exchanger for Initial CommissioningTop View Rear Preparations for ConnectingCondensed Water Connection FrontElectrical Connection Sealing the CabinetServicing and Maintenance Fan ReplacementGeneral Inspection on Fans-Annual Reinstall the fan by reversing the steps to remove the fan Inspect the Heat Exchanger-AnnualHeat exchanger replacement Replacing the Heat ExchangerDismantling and Disposal Water Purity Requirements Prevalent impurities and removal methodsSuggested hydrologic levels Unit Installation Checklist Nominal values at setup site Commissioning CertificateXDK Commissioning certificate Configuration Type of cabinetControl of status Cold water facility on site Electrical data / documentsFunction check GPM Water Purity Requirements Page Ti n Ne tIti That