GarrettCom 6K32 B4.0 Installation, B4.1 UL Requirements for DC-powered units, B5.0 Operation

Page 61

Magnum 6K32 Managed Switch

Installation and User Guide (02/05)

failure. It is also frequently used for computer system backup, management and operations monitoring equipment.

The 24VDC and 125VDC solution are particularly useful in the Industrial environment, where it is common facilities to operate on 24VDC or 125VDC power. The 125VDC solution is mainly used in power utilities, such as electrical substations, electrical generating plants, etc. The 24VDC applications are mainly in the Industrial environment, such as factory floor, HVAC equipment, military equipment, etc.

B4.0 INSTALLATION

This section describes the installation of the -48 VDC, 24VDC and 125VDC power source leads to the -48 VDC, 24VDC and 125VDC power terminal block on the Magnum 6K32s. (see figure at right).

In this picture, the -48VDC terminal block on the Magnum 6K32 is located on the rear of the unit and is equipped with three (3) screw-down lead posts. It is similar for 24VDC and 125VDC options on Magnum 6K32. The leads are identified as negative (-), positive (+), and chassis ground (GND).

Figure B4.0: -48VDC Terminal Block on Magnum 6K32-48VDC

The actual connection procedure is very straightforward. Simply connect the leads to the Magnum unit, beginning with ground. Ensure that each lead is securely tightened.

Note: The GND should be hooked up first. The 6K32 unit has a floating ground, so the user may elect to Ground either + or = terminal to suit the customer’s use.

Before connecting hot lines to the Terminal Block of –48VDC, 24VDC or 125VDC, always use a digital voltmeter to measure the output voltage of the power supply and determine the lead which is more “+ve potential”. The more “+ve” voltage lead from 48V or –48V supply must be connected to the post labeled “+”.

An ON-OFF manual switch is optional for DC power. This can be used to cut off power connections and as a RESET for the Magnum 6K32 Switch.

B4.1 UL Requirements for DC-powered units

1.Minimum 18AWG cable for connection to a Centralized DC power source.

2.Minimum 14AWG cable for connection to a earthing wiring.

3.Use only with Listed 10 A circuit breaker provided in building installation.

4.“Complies with FDA radiation performance standards, 21 CFR subchapter J.” or equivalent.

5.Fastening torque of the lugs on the terminal block: 9 inch-pound max.

6.Centralized DC Power Source cable securement, use at least four cable ties to secure the cable to the rac,k at least 4 inches apart, with the first one located within 6 inches of the terminal block.

B5.0 OPERATION

www . GarrettCom . com

55

Image 61
Contents Corporate Headquarters GarrettCom, IncTrademarks Contacting GarrettCom, Inc Table of ContentsCanadian Emission Introduction Troubleshooting Personal Hubs, 10Mb series Personal Switches, 10/100MbTechnical Specifications Management Console connector Fiber connector types supportedPower Supply Internal DC Power Supply OptionsManual switches for modular slot port module only Alarm Contact OptionalAgency Approvals Ordering Information Gigabit Transceiver options 6KP8-45-2MT 6KP8-45-2SLC LC connectorsIntroduction Inspecting the Package and Product Product Description Magnum 6K32 Managed Switch Magnum 6K32 and 6K32R chassis Eight-port SFF fiber modules 6K8-MTRJ, 6K8-MLC, 100Mb fiber Mode for best fiber distance100Mb fiber eight Port modules for the Magnum @ RJ-45 + 2@ 100Mb SC Eight-Port Copper Module, 6K8-RJ45@ RJ-45 + 2@ 100Mb ST Four-Port 10 Mb mm Fiber ST Modules Packet Prioritization, 802.1p QOS Gigabit 1000Mbps port modulesFrame Buffering and Flow Control Managed Network Software MNS-6K for Magnum 6K32 „ Managed switching for high performance Ethernet LANs Features and Benefits„ Features Fiber-Built-In Applications Example 1 Magnum 6K32 Switch for a Vlan applicationInternet Internet Example 3 Redundant ApplicationSwitch #1 Locating Magnum 6K32 Switches InstallationConnecting Ethernet Media Connecting Fiber Optic SC-type, Snap-In Connecting Fiber Optic ST-type, twist-lockIeee Standard Media Type Max. Distance Port Module Fiber CopperMedia Ieee Standard Connecting Single-Mode Fiber OpticRack-mounting for 19 Retma racks, regular Magnum 6K32s Table-Top or Shelf MountingMagnum 6K32 unit. These 1 Mountings for Magnum 6K32 units rack-mounted in a frame Rack-mounting, Reverse version of the Magnum 6K32s2 Reverse Magnum 6K32 units, rack- mounted in a frame Powering the Magnum 6K32 Managed SwitchPreparation for Installing and Removing 6KPMs 6K32 Port Module 6KPM Installation1a Removing front panel after the screws being removed Remove Chassis Cover1b Pulling out the top coved from the chassis base 1d Top View 6KPM retaining screws hold Face Plate Installing 6KPM Cards in the Magnum 6K32Securely latching up 6KPM Cards into a Magnum 6K32 Removing 6KPM Cards 2g Top View 6KPM Module installed inside a 6K32 SwitchRemoving a 6KPM Card Pin Signal Description Connecting the Console Terminal to Magnum 6K32 ManagementDB-9 Console port connector Console DB-9 PortFiltering and Forwarding Switching FunctionalityAuto-Cross MDIXAuto-negotiation, for 10/100Mbps RJ-45 ports Status LEDsPWR ACTWww . GarrettCom . com Flow-control, Ieee 802.3x standard ’cvr 6KP4Magnum 6K32 Managed Switch Port Modules 6KPM Module Description 1b 6KP4-F10ST, 4@10Mb multi-mode FX-ST twist lock Module As 10Mb Half-duplex by Default for 10Mb fiber Connectors and configuredMagnum 6KP4 Flstfx is a combo fiberEquipped with 4 dual speed Mode SC-type connectors. ItCopper ports and 2 Single Provides an advantage Through combining copperWww . GarrettCom . com Activity FULL/HALF Port@ 100Mbps Multi-Mode Fiber portLink Module is a combo module with Magnum 6KP8-45MTCopper and fiber Small Form Factor Placing more ports on one module9 6KP8-RJ45 Twisted Pair, 10/100Mb 8-Port 10a 6KP8-45-2LC, 6@ 10/100Mbps RJ-45 and 2@100Mb single-mode FX , LC Small-Form-Factor GBIC-SXSC Gigabit fiber1000Mb, multi-mode SC Connector12 6KM-BLNK 11a GBIC-LXSC Gigabit fiber 1000Mb, multi-mode SC Connector@ 1000Mb Fiber SC + 2@ 100Mb SC Before Calling for Assistance When Calling for AssistanceNo Problem Found Return Material Authorization RMA ProcedureB1.0 Specifications for Magnum 6K32 SWITCHES, DC Power Appendix B Internal DC Power Supply OptionsPower Supply Internal -48VDC Option Shipping and Packaging InformationB3.0 Applications for DC Powered Switches Power Supply Internal 125 VDC Option Industrial ApplicationsB4.1 UL Requirements for DC-powered units B4.0 InstallationB5.0 Operation B6.0 Ordering Information B7.0 TroubleshootingGND Appendix C Internal DC Dual-Source Power OptionC5.0 Installation C4.0 Features and Benefits of the DUAL-SOURCE DesignC6.0 Ordering Information C5.1 UL RequirementsExample Magnum 6K32R-48VDC Example Magnum 6K32R-24VDC or Magnum 6K32R-125VDC