Falcon FN4KRM-2TXI, FN6KRM-2TXI UPS Input Power Requirements, UPS Input/Output Requirements

Page 10

4.2 UPS Input Power Requirements

a.VERIFY THE PROPER UPS INPUT POWER IS AVAILABLE (for each UPS installed)

FN3KRM-2TXI

Input

--

Hardwire, 208-240Vac, 50/60Hz, 20A, single-phase, 2 wire plus ground

FN4KRM-2TXI

Input

--

Hardwire, 208-240Vac, 50/60Hz, 30A, single-phase, 2 wire plus ground

FN5KRM-2TXI

Input

--

Hardwire, 208-240Vac, 50/60Hz, 30A, single-phase, 2 wire plus ground

FN6KRM-2TXI

Input

--

Hardwire, 208-240Vac, 50/60Hz, 40A, single-phase, 2 wire plus ground

4.3 UPS Input/Output Requirements

a.VERIFY THE INPUT AND OUTPUT WIRING REQUIREMENTS

FN3KRM-2TXI

Wiring Type -- THHN, 600V, insulated solid copper wire

 

Gage

-- Input, 12 awg. - Output, 10 awg.

 

Terminal Block Screw Torque -- 20 inch-pounds

 

Required Branch Rated input circuit breaker -- 20A (40A with 3 external battery charger module

 

 

options installed)

 

Required Branch Rated output circuit breaker -- 20A

FN4KRM-2TXI

Wiring Type -- THHN, 600V, insulated solid copper wire

 

Gage

-- Input, 10 awg. - Output, 8 awg.

 

Terminal Block Screw Torque -- 20 inch-pounds

 

Required Branch Rated input circuit breaker -- 30A (50A with 3 external battery charger module

 

 

options installed)

 

Required Branch Rated output circuit breaker -- 30A

FN5KRM-2TXI

Wiring Type -- THHN, 600V, insulated solid copper wire

 

Gage

-- Input, 10 awg. - Output, 8 awg.

 

Terminal Block Screw Torque -- 20 inch-pounds

 

Required Branch Rated input circuit breaker -- 30A (50A with 3 external battery charger module

 

 

options installed)

 

Required Branch Rated output circuit breaker -- 30A

FN6KRM-2TXI

Wiring Type -- THHN, 600V, insulated solid copper wire

 

Gage

-- Input, 8 awg. - Output, 4 awg.

 

Terminal Block Screw Torque -- 25-30 inch-pounds

 

Required Branch Rated input circuit breaker -- 40A (60A with 3 external battery charger module

 

 

options installed)

 

Required Branch Rated output circuit breaker -- 40A

10

Image 10
Contents Owners Operating Manual Table of Contents FN SeriesTM Parallelable and N+1 Redundant UPS Features FN -2TXI Model Double Conversion On-line UPS Block DiagramInstallation Storage and TransportationIntroduction Manual Overview FN Rackmount OverviewDC/DC Converter Input & Power Factor CorrectionDC/AC Inverter Static Bypass Function Battery PacksInternal Battery Charger Automatic Bypass TransfersFNITRM-2 Rackmount Output Transformer Module Unpacking the UPS and Battery BankFN Rackmount UPS Module FNBRM-1S7 Battery Module System unit receivedPRE-INSTALLATION Details Floor Loading RequirementsUPS Input Power Requirements UPS Input/Output RequirementsUPS Output Rating Details FN Rackmount System Rear Panel OverviewPage Page Page Control Button Operation Display & ControlsControl Button and LCD Locations Control PanelLED Display Modes LCD Display Overview Status and Error Code DescriptionsLCD Icon Descriptions Page How to start up the UPS with utility power present OperationPage How to completely shutdown the UPS How to display readings Page How to Display Programmed Settings Page Fixed or constant frequency How to Change the Programmed Settings Page Page Shows the UPS unit address. If Page Advanced Communications Option Cards Available CommunicationsModels UPS & PC Computer DB-9 pin designations are as followsUPS Side RS-232C Interface Computer Side Optional Remote Emergency Power Off RepoOptional Communications Interface Board Details UA88383 Dry Contact Interface Option Card UA88382 USB Interface Option CardUsha SNMP/HTTP Agent Option Card Maintenance UPS and Battery CareParallel Mode Operation Environmental Recycling the Used Battery PacksFCC Considerations Technical Support Requesting Technical Information or SupportNEW Product Limited Warranty Falcon ELECTRIC, INCFN SeriesTM UPS Plus 3kVA 12kVA FN SeriesTM UPS Plus 4kVA 16kVA FN SeriesTM UPS Plus 5kVA 20kVA FN SeriesTM UPS Plus 6kVA 24kVA