8.0 MAINTENANCE

The FN Series UPS requires very little maintenance. The batteries are located inside the battery module and consist of (20) Yuasa 12V, 7AH or equivalent, sealed, VRLA, maintenance-free, lead-acid batteries.

Batteries must be kept recharged to prevent excessive self-discharging, which may result in their premature failure. When connected to the battery module, the UPS will continuously recharge the bat- teries when plugged in and turned on. When not in use, batteries must be recharged every 6 months to keep your warranty valid.

1. The UPS and Battery Care

Keep the area around the UPS clean and dust free. If the area around the UPS becomes very dusty, clean it with a vacuum cleaner. To assure the full 3-5 year battery life, keep the UPS battery module at an ambient temperature of 77ºF (25ºC). Other than replacement at three to five years of service, no other battery maintenance is required.

2. Storing the UPS and Batteries

When storing the UPS for any amount of time, it is recommended to connect the battery module and turn on the UPS for at least 24 hours, every four to six months to ensure full recharging of the batteries. This will pre- vent excessive battery self-discharge.

3. When to Replace Batteries

We suggest the battery pack(s) be replaced every 3-5 years for FN units that are operated and maintained in a 77ºF (25ºC) environment. Higher temperature operating environments will decrease the battery life. Typically, if the UPS is installed in a 104ºF (40ºC) or above operating environment, the batteries will need to be replaced once a year.

In order to assure the performance of the FN Series UPS, check the battery every two to three months by performing a UPS self-test. If at any time the UPS LCD panel displays the weak or defective battery icon or error code, the batteries need replacing. Contact the Falcon Electric Service Department to order replacement batteries.

4. Battery Replacement

Battery replacement inside the battery module must be performed by a qualified service technician. Contact Falcon service when battery replacement is required.

NOTE!

NEVER ATTEMPT TO REPLACE THE BATTERY PACKS WHILE THE UPS IS IN BATTERY MODE.

35

Image 35
Contents Owners Operating Manual Table of Contents FN -2TXI Model Double Conversion On-line UPS Block Diagram FN SeriesTM Parallelable and N+1 Redundant UPS FeaturesStorage and Transportation InstallationFN Rackmount Overview Introduction Manual OverviewDC/AC Inverter Input & Power Factor CorrectionDC/DC Converter Automatic Bypass Transfers Battery PacksInternal Battery Charger Static Bypass FunctionSystem unit received Unpacking the UPS and Battery BankFN Rackmount UPS Module FNBRM-1S7 Battery Module FNITRM-2 Rackmount Output Transformer ModuleFloor Loading Requirements PRE-INSTALLATION DetailsUPS Input/Output Requirements UPS Input Power RequirementsFN Rackmount System Rear Panel Overview UPS Output Rating DetailsPage Page Page Control Panel Display & ControlsControl Button and LCD Locations Control Button OperationLED Display Modes LCD Icon Descriptions Status and Error Code DescriptionsLCD Display Overview Page Operation How to start up the UPS with utility power presentPage How to completely shutdown the UPS How to display readings Page How to Display Programmed Settings Page Fixed or constant frequency How to Change the Programmed Settings Page Page Shows the UPS unit address. If Page UPS & PC Computer DB-9 pin designations are as follows CommunicationsModels Advanced Communications Option Cards AvailableOptional Communications Interface Board Details Optional Remote Emergency Power Off RepoUPS Side RS-232C Interface Computer Side Usha SNMP/HTTP Agent Option Card UA88382 USB Interface Option CardUA88383 Dry Contact Interface Option Card UPS and Battery Care MaintenanceParallel Mode Operation FCC Considerations Recycling the Used Battery PacksEnvironmental Requesting Technical Information or Support Technical SupportFalcon ELECTRIC, INC NEW Product Limited WarrantyFN SeriesTM UPS Plus 3kVA 12kVA FN SeriesTM UPS Plus 4kVA 16kVA FN SeriesTM UPS Plus 5kVA 20kVA FN SeriesTM UPS Plus 6kVA 24kVA