Falcon FN4KRM-2TXI, FN6KRM-2TXI, FN3KRM-2TXI manual

Page 18

Er04 --

Error code 04 indicates the UPS inverter has malfunctioned. Contact Falcon Service.

Er05 --

Error code 05 indicates the UPS batteries are weak or dead and must be replaced.

 

Call Falcon Service upon receiving the message for further instructions.

Er06 --

Error code 06 indicates the UPS output has a short circuit connected to it.

 

Remove the connected equipment load from the UPS output and restart the UPS. If the

 

shorted output condition is corrected, determine the location of the shorted wiring or

 

equipment.

Er07 --

EPO Mode.

Er08 --

DC Bus high voltage level out of specification. Contact Falcon Service.

Er09 --

DC Bus low voltage level out of specification. Contact Falcon Service.

Er10 --

Error code 10 indicates the UPS inverter has encountered an over-current condition.

 

This could indicate the connected equipment exceeds the output rating of the UPS.

 

Disconnect some of the connected equipment in an attempt to correct the condition.

Er11 --

Error code 11 indicates the UPS is in an over-temperature condition. Verify the ambient

 

operating temperature is not too high. Verify the UPS cooling fan operation.

Er12 --

Error code 12 indicates the UPS output is overloaded, similar to error code 10. This could

 

indicate the connected equipment exceeds the output rating of the UPS.

 

Disconnect some of the connected equipment in an attempt to correct the condition.

Er13 --

Battery charger malfunction. Contact Falcon Service.

Er14 --

Cooling fan failure. Contact Falcon Service.

Er15 --

Maintenance bypass initiated improperly. Refer to page 31, Maintenance Bypass section.

Er18 --

Internal software error, UPS programming reset to default values.

Er22 --

Static bypass malfunction. Contact Falcon Service.

Er24 --

Fixed 50 or 60Hz output mode programmed without turning off the bypass input circuit breaker

 

Should a fixed 50 or 60Hz output be desired, turn the bypass input circuit breaker off. To clear

 

error code 24, startup the UPS with the Bypass input circuit breaker turned off.

Er26 --

PFC over-current condition. Verify the UPS output is or has been overloaded.

Er28 --

The UPS output has experienced a 120% overload in bypass for over 2 minutes.

 

Bypass has been shutdown.

Er29 --

The battery charger is overcharging the batteries. Contact Falcon Service.

Er** --

Other error code, consult with Falcon Service.

18

Image 18
Contents Owners Operating Manual Table of Contents FN SeriesTM Parallelable and N+1 Redundant UPS Features FN -2TXI Model Double Conversion On-line UPS Block DiagramInstallation Storage and TransportationIntroduction Manual Overview FN Rackmount OverviewInput & Power Factor Correction DC/DC ConverterDC/AC Inverter Static Bypass Function Battery PacksInternal Battery Charger Automatic Bypass TransfersFNITRM-2 Rackmount Output Transformer Module Unpacking the UPS and Battery BankFN Rackmount UPS Module FNBRM-1S7 Battery Module System unit receivedPRE-INSTALLATION Details Floor Loading RequirementsUPS Input Power Requirements UPS Input/Output RequirementsUPS Output Rating Details FN Rackmount System Rear Panel OverviewPage Page Page Control Button Operation Display & ControlsControl Button and LCD Locations Control PanelLED Display Modes Status and Error Code Descriptions LCD Display OverviewLCD Icon Descriptions Page How to start up the UPS with utility power present OperationPage How to completely shutdown the UPS How to display readings Page How to Display Programmed Settings Page Fixed or constant frequency How to Change the Programmed Settings Page Page Shows the UPS unit address. If Page Advanced Communications Option Cards Available CommunicationsModels UPS & PC Computer DB-9 pin designations are as followsOptional Remote Emergency Power Off Repo UPS Side RS-232C Interface Computer SideOptional Communications Interface Board Details UA88382 USB Interface Option Card UA88383 Dry Contact Interface Option CardUsha SNMP/HTTP Agent Option Card Maintenance UPS and Battery CareParallel Mode Operation Recycling the Used Battery Packs EnvironmentalFCC Considerations Technical Support Requesting Technical Information or SupportNEW Product Limited Warranty Falcon ELECTRIC, INCFN SeriesTM UPS Plus 3kVA 12kVA FN SeriesTM UPS Plus 4kVA 16kVA FN SeriesTM UPS Plus 5kVA 20kVA FN SeriesTM UPS Plus 6kVA 24kVA