Falcon FN4KRM-2TXI, FN6KRM-2TXI, FN3KRM-2TXI PRE-INSTALLATION Details, Floor Loading Requirements

Page 9

4.0PRE-INSTALLATION DETAILS

Falcon Electric, Inc. is not responsible for shipping damage or for filing shipping damage claims. Visually inspect the equipment for freight damage. If any equipment has been damaged during shipment, retain the shipping pallet and packing materials for inspection by the carrier, and immediately file a claim for “shipping damage” with the carrier. If you discover damage after acceptance, file a claim for “concealed damage”.

To file a claim for shipping damage or concealed damage:

a.YOU MUST file with the carrier within 15 days of receipt of the equipment;

b.YOU MUST send a copy of the damage claim within 15 days to Falcon Electric, Inc.

WARNING

The UPS, Transformer and Battery Modules are very heavy. Use the proper lifting equipment and take the proper precautions when lifting or moving them.

1.Always install the FN system indoors in a controlled environment.

2. Install the FN modules in a location with unrestricted airflow around the front and rear sides of the modules, away from water, flammable liquids, gases, corrosive, and conductive contaminants.

3.Maintain a minimum clearance of 4 inches in the front and rear of the UPS.

4.Maintain an ambient temperature range of 32ºF to 104ºF (0ºC to 40ºC). To assure the maximum life of the batteries, operation in an ambient temperature of 68ºF to 77ºF (20ºC to 25ºC) is recommended.

OPERATION IN TEMPERATURES ABOVE 77ºF (25ºC) WILL REDUCE BATTERY LIFE.

5.The FN Series Rackmount system modules must be installed in a standard 19” equipment rack having hard mounted shelves under the modules to properly support their weight.

6.When selecting a suitable rack location for the UPS, Transformer and battery bank(s) always verify the floor loading capabilities:

4.1 Floor Loading Requirements

a. VERIFY THE FLOOR OR SUPPORTING SURFACE UNDER THE EQUIPMENT RACK IS RATED TO SUPPORT THE WEIGHT OF THE TOTAL WEIGHT OF THE RACK, THE FN MODULES AND ALL OTHER EQUIPMENT INSIDE THE RACK.

UPS Module:

(1)FN3KRM-2TXI or FN4KRM-2TXI or FN5KRM-2TXI or FN6KRM-2TXI = 53 lbs. (24 kg)

(2)FN3KRM-2TXI or FN4KRM-2TXI or FN5KRM-2TXI or FN6KRM-2TXI = 106 lbs. (48 kg)

(3)FN3KRM-2TXI or FN4KRM-2TXI or FN5KRM-2TXI or FN6KRM-2TXI = 159 lbs. (72 kg)

(4)FN3KRM-2TXI or FN4KRM-2TXI or FN5KRM-2TXI or FN6KRM-2TXI = 212 lbs. (96 kg)

Battery Bank Modules (for all FN Rackmount models)

(1)FNBRM-1S7 = 150 lbs. (68 kg)

(2)FNBRM-1S7 = 300 lbs. (136 kg)

(3)FNBRM-1S7 = 450 lbs. (204 kg)

(4)FNBRM-1S7 = 600 lbs. (272 kg)

Output Transformer Module (for all FN Rackmount models)

(1)FNITRM-2 = 91 lbs. (41 kg)

(2)FNITRM-2= 181 lbs. (82 kg)

(3)FNITRM-2= 272 lbs. (123 kg)

(4)FNITRM-2= 362 lbs. (164 kg)

9

Image 9
Contents Owners Operating Manual Table of Contents FN -2TXI Model Double Conversion On-line UPS Block Diagram FN SeriesTM Parallelable and N+1 Redundant UPS FeaturesStorage and Transportation InstallationFN Rackmount Overview Introduction Manual OverviewInput & Power Factor Correction DC/DC ConverterDC/AC Inverter Internal Battery Charger Battery PacksStatic Bypass Function Automatic Bypass TransfersFN Rackmount UPS Module FNBRM-1S7 Battery Module Unpacking the UPS and Battery BankFNITRM-2 Rackmount Output Transformer Module System unit receivedFloor Loading Requirements PRE-INSTALLATION DetailsUPS Input/Output Requirements UPS Input Power RequirementsFN Rackmount System Rear Panel Overview UPS Output Rating DetailsPage Page Page Control Button and LCD Locations Display & ControlsControl Button Operation Control PanelLED Display Modes Status and Error Code Descriptions LCD Display OverviewLCD Icon Descriptions Page Operation How to start up the UPS with utility power presentPage How to completely shutdown the UPS How to display readings Page How to Display Programmed Settings Page Fixed or constant frequency How to Change the Programmed Settings Page Page Shows the UPS unit address. If Page Models CommunicationsAdvanced Communications Option Cards Available UPS & PC Computer DB-9 pin designations are as followsOptional Remote Emergency Power Off Repo UPS Side RS-232C Interface Computer SideOptional Communications Interface Board Details UA88382 USB Interface Option Card UA88383 Dry Contact Interface Option CardUsha SNMP/HTTP Agent Option Card UPS and Battery Care MaintenanceParallel Mode Operation Recycling the Used Battery Packs EnvironmentalFCC Considerations Requesting Technical Information or Support Technical SupportFalcon ELECTRIC, INC NEW Product Limited WarrantyFN SeriesTM UPS Plus 3kVA 12kVA FN SeriesTM UPS Plus 4kVA 16kVA FN SeriesTM UPS Plus 5kVA 20kVA FN SeriesTM UPS Plus 6kVA 24kVA