Falcon FN6KRM-2TXI, FN4KRM-2 manual Operation, How to start up the UPS with utility power present

Page 19

6.0 OPERATION

The following sections outline the operation and programming of the FN -2TXI UPS models. Please read and understand them completely prior to connecting any equipment to the UPS output.

6.1How to start up the UPS with utility power present

1.Verify the UPS input wiring is correct and connected to a live circuit.

2.Turn on the UPS and Bypass input circuit breakers located on the UPS rear panel, and the following LCD Display will be displayed. The UPS output will be immediately turned on, with the UPS in bypass mode.

Display A is an LCD test display and is shown for about 3 seconds after the input circuit breaker is turned on.

Next, display B is shown (OFF or BPS displayed). The UPS is OFF with the load supported by the bypass output. The UPS will remain in this state until the “On” button is depressed. When the UPS is turned off using the “Off” button, it will return to this state until the input circuit breaker is turned off.

3.Depress the “On” button for 3 seconds until two audible beeps are sounded.

4.The UPS fans will turn on and the following LCD display will be shown:

Note the MIMIC portion of the display with the arrow under the line and the input voltage is displayed.

The UPS will sound two short beeps continuously until the following is displayed.

NOTE: Always allow the UPS to charge its batteries for 8 hours prior to use.

5. The UPS will now sequence up to on-line mode and display the following:

The UPS initiates a self-test.

Go to the next page.

19

Image 19
Contents Owners Operating Manual Table of Contents FN -2TXI Model Double Conversion On-line UPS Block Diagram FN SeriesTM Parallelable and N+1 Redundant UPS FeaturesStorage and Transportation InstallationFN Rackmount Overview Introduction Manual OverviewDC/DC Converter Input & Power Factor CorrectionDC/AC Inverter Automatic Bypass Transfers Battery PacksInternal Battery Charger Static Bypass FunctionSystem unit received Unpacking the UPS and Battery BankFN Rackmount UPS Module FNBRM-1S7 Battery Module FNITRM-2 Rackmount Output Transformer ModuleFloor Loading Requirements PRE-INSTALLATION DetailsUPS Input/Output Requirements UPS Input Power RequirementsFN Rackmount System Rear Panel Overview UPS Output Rating DetailsPage Page Page Control Panel Display & ControlsControl Button and LCD Locations Control Button OperationLED Display Modes LCD Display Overview Status and Error Code DescriptionsLCD Icon Descriptions Page Operation How to start up the UPS with utility power presentPage How to completely shutdown the UPS How to display readings Page How to Display Programmed Settings Page Fixed or constant frequency How to Change the Programmed Settings Page Page Shows the UPS unit address. If Page UPS & PC Computer DB-9 pin designations are as follows CommunicationsModels Advanced Communications Option Cards AvailableUPS Side RS-232C Interface Computer Side Optional Remote Emergency Power Off RepoOptional Communications Interface Board Details UA88383 Dry Contact Interface Option Card UA88382 USB Interface Option CardUsha SNMP/HTTP Agent Option Card UPS and Battery Care MaintenanceParallel Mode Operation Environmental Recycling the Used Battery PacksFCC Considerations Requesting Technical Information or Support Technical SupportFalcon ELECTRIC, INC NEW Product Limited WarrantyFN SeriesTM UPS Plus 3kVA 12kVA FN SeriesTM UPS Plus 4kVA 16kVA FN SeriesTM UPS Plus 5kVA 20kVA FN SeriesTM UPS Plus 6kVA 24kVA