Falcon FN4KRM-2TXI, FN6KRM-2TXI, FN3KRM-2TXI manual How to completely shutdown the UPS

Page 21

6.2How to start up the UPS without utility power present (Cold Start)

1.Press the “On” button for 6 seconds to awaken the UPS. The UPS will beep twice and display G below. Immediately upon G being displayed, press the “On” button for another 6 seconds. The UPS will beep twice again and sequence through H and I.

After depressing the “On” button for 6 seconds the first time, the UPS will beep twice and “OFF” or “BPS” will be displayed.

After depressing the “On” button the second time for 6 seconds, the UPS will display input voltage H and I. The UPS output voltage will be present and the UPS will continue to run on battery until the batteries are discharged or the “Off” button is pressed for 3 seconds.

6.3How to turn off the UPS inverter and place the UPS into bypass mode

1.While the UPS is operating in utility, inverter or battery mode, depress the “Off” button until the UPS sounds two audible beeps. The UPS will switch to static bypass and turn off the inverter. The LCD will display “OFF” or “BPS”. The connected load will now be powered directly from the utility source. The UPS will continue to operate in bypass mode until:

a.The “On” button is depressed for three seconds, which will return the UPS to normal inverter mode operation.

b.The UPS and Bypass Input circuit breakers are turned off, which will shut down the UPS and the connected load completely.

6.4How to completely shutdown the UPS

1.While the UPS is operating in utility, inverter or battery mode, depress the “Off” button until the UPS

sounds two audible beeps. The UPS will switch to static bypass and turn off the inverter. The LCD will display “OFF” or “BPS”.

2.Turn off the UPS and Bypass input circuit breakers, which will shutdown the UPS and the connected load completely.

Note, the UPS may continue to run for 30 seconds to one minute prior to turning off.

21

Image 21
Contents Owners Operating Manual Table of Contents FN -2TXI Model Double Conversion On-line UPS Block Diagram FN SeriesTM Parallelable and N+1 Redundant UPS FeaturesStorage and Transportation InstallationFN Rackmount Overview Introduction Manual OverviewInput & Power Factor Correction DC/DC ConverterDC/AC Inverter Internal Battery Charger Battery PacksStatic Bypass Function Automatic Bypass TransfersFN Rackmount UPS Module FNBRM-1S7 Battery Module Unpacking the UPS and Battery BankFNITRM-2 Rackmount Output Transformer Module System unit receivedFloor Loading Requirements PRE-INSTALLATION DetailsUPS Input/Output Requirements UPS Input Power RequirementsFN Rackmount System Rear Panel Overview UPS Output Rating DetailsPage Page Page Control Button and LCD Locations Display & ControlsControl Button Operation Control PanelLED Display Modes Status and Error Code Descriptions LCD Display OverviewLCD Icon Descriptions Page Operation How to start up the UPS with utility power presentPage How to completely shutdown the UPS How to display readings Page How to Display Programmed Settings Page Fixed or constant frequency How to Change the Programmed Settings Page Page Shows the UPS unit address. If Page Models CommunicationsAdvanced Communications Option Cards Available UPS & PC Computer DB-9 pin designations are as followsOptional Remote Emergency Power Off Repo UPS Side RS-232C Interface Computer SideOptional Communications Interface Board Details UA88382 USB Interface Option Card UA88383 Dry Contact Interface Option CardUsha SNMP/HTTP Agent Option Card UPS and Battery Care MaintenanceParallel Mode Operation Recycling the Used Battery Packs EnvironmentalFCC Considerations Requesting Technical Information or Support Technical SupportFalcon ELECTRIC, INC NEW Product Limited WarrantyFN SeriesTM UPS Plus 3kVA 12kVA FN SeriesTM UPS Plus 4kVA 16kVA FN SeriesTM UPS Plus 5kVA 20kVA FN SeriesTM UPS Plus 6kVA 24kVA