6.8 How to Use the Maintenance Bypass Switch Located on the Rear Panel

IMPORTANT: Improper use of the internal Maintenance Bypass Switch will void the equipment warranty. The following instructions must be followed whenever this switch is used.

1.Press the”Off/Bypass” button for 5 seconds to place the UPS into bypass mode.

2.On the rear of the transformer module, remove the two phillips screws securing the upper and lower sides of the maintenance bypass security cover plate.

3.On the rear of the transformer module, turn the Maintenance Bypass Switch to “Bypass”. The maintenance bypass icon will be displayed on the LCD display.

4.The output transformer is now in maintenance bypass mode.

5.To return to normal UPS mode operation, switch the Maintenance Bypass Switch to INV. Replace the switch cover plate and secure it with the screws previously removed.

6.Press the “On” button on the UPS module to return the UPS to normal inverter operation.

31

Image 31
Contents Owners Operating Manual Table of Contents FN -2TXI Model Double Conversion On-line UPS Block Diagram FN SeriesTM Parallelable and N+1 Redundant UPS FeaturesStorage and Transportation InstallationFN Rackmount Overview Introduction Manual OverviewDC/DC Converter Input & Power Factor CorrectionDC/AC Inverter Automatic Bypass Transfers Battery PacksInternal Battery Charger Static Bypass FunctionSystem unit received Unpacking the UPS and Battery BankFN Rackmount UPS Module FNBRM-1S7 Battery Module FNITRM-2 Rackmount Output Transformer ModuleFloor Loading Requirements PRE-INSTALLATION DetailsUPS Input/Output Requirements UPS Input Power RequirementsFN Rackmount System Rear Panel Overview UPS Output Rating DetailsPage Page Page Control Panel Display & ControlsControl Button and LCD Locations Control Button OperationLED Display Modes LCD Display Overview Status and Error Code DescriptionsLCD Icon Descriptions Page Operation How to start up the UPS with utility power presentPage How to completely shutdown the UPS How to display readings Page How to Display Programmed Settings Page Fixed or constant frequency How to Change the Programmed Settings Page Page Shows the UPS unit address. If Page UPS & PC Computer DB-9 pin designations are as follows CommunicationsModels Advanced Communications Option Cards AvailableUPS Side RS-232C Interface Computer Side Optional Remote Emergency Power Off RepoOptional Communications Interface Board Details UA88383 Dry Contact Interface Option Card UA88382 USB Interface Option CardUsha SNMP/HTTP Agent Option Card UPS and Battery Care MaintenanceParallel Mode Operation Environmental Recycling the Used Battery PacksFCC Considerations Requesting Technical Information or Support Technical SupportFalcon ELECTRIC, INC NEW Product Limited WarrantyFN SeriesTM UPS Plus 3kVA 12kVA FN SeriesTM UPS Plus 4kVA 16kVA FN SeriesTM UPS Plus 5kVA 20kVA FN SeriesTM UPS Plus 6kVA 24kVA