Falcon FN4KRM-2TXI, FN6KRM-2TXI, FN3KRM-2TXI manual Fixed or constant frequency

Page 26

 

 

 

 

Fixed or constant frequency

 

 

 

 

output mode: In normal mode

 

 

 

 

the UPS output frequency will

 

 

 

 

automatically be set to the

 

 

 

 

utility frequency and is

 

 

 

 

synchronized with that

 

 

 

 

frequency. When set to cf50Hz

 

 

 

 

mode, the UPS inverter output

 

 

 

 

frequency will always be 50Hz.

 

 

 

 

When set to cf60Hz mode, the

 

 

 

 

UPS inverter output frequency

 

 

 

 

will always be 60Hz.

 

 

 

 

Setting the UPS to a fixed or

 

 

 

 

constant output frequency

 

 

 

 

should be done when the input

 

 

 

 

source is a generator.

 

 

 

 

Depress the “Next Page”

 

 

 

 

 

 

 

 

 

 

 

 

button.

 

 

 

 

The next parameter displayed

 

 

 

 

shows the inverter output

 

 

 

 

voltage adjustment. The

 

 

 

 

adjustment can be set to 0%

 

 

 

 

(shown), +1%, -1%, +2%, -2%,

 

 

 

 

+3%or -3% (not shown).

 

 

 

 

Depress the “Next Page”

 

 

 

 

button.

X

 

 

The next parameter displayed

shows the UPS unit address. If only one UPS is being used, the address should be set to “d0” as shown.

If multiple parallel UPS units are connected in a parallel configuration of 6, 12, 18 or 24kVA, or 6, 12, 18kVA N+1 operation, the units would be addressed “d0”, “d1”, “d2” and “d3”. See the parallel mode configuration section on page 30 of this manual for more details.

Depress the “Next Page” button.

The next parameter displayed shows the UPS position when it is used in a parallel configuration. The positions are “01”, “02”, “03”, or “04”.

If only one UPS is being configured, the position should be set to “01” as shown.

26

Image 26
Contents Owners Operating Manual Table of Contents FN SeriesTM Parallelable and N+1 Redundant UPS Features FN -2TXI Model Double Conversion On-line UPS Block DiagramInstallation Storage and TransportationIntroduction Manual Overview FN Rackmount OverviewDC/AC Inverter Input & Power Factor CorrectionDC/DC Converter Static Bypass Function Battery PacksInternal Battery Charger Automatic Bypass TransfersFNITRM-2 Rackmount Output Transformer Module Unpacking the UPS and Battery BankFN Rackmount UPS Module FNBRM-1S7 Battery Module System unit receivedPRE-INSTALLATION Details Floor Loading RequirementsUPS Input Power Requirements UPS Input/Output RequirementsUPS Output Rating Details FN Rackmount System Rear Panel OverviewPage Page Page Control Button Operation Display & ControlsControl Button and LCD Locations Control PanelLED Display Modes LCD Icon Descriptions Status and Error Code DescriptionsLCD Display Overview Page How to start up the UPS with utility power present OperationPage How to completely shutdown the UPS How to display readings Page How to Display Programmed Settings Page Fixed or constant frequency How to Change the Programmed Settings Page Page Shows the UPS unit address. If Page Advanced Communications Option Cards Available CommunicationsModels UPS & PC Computer DB-9 pin designations are as followsOptional Communications Interface Board Details Optional Remote Emergency Power Off RepoUPS Side RS-232C Interface Computer Side Usha SNMP/HTTP Agent Option Card UA88382 USB Interface Option CardUA88383 Dry Contact Interface Option Card Maintenance UPS and Battery CareParallel Mode Operation FCC Considerations Recycling the Used Battery PacksEnvironmental Technical Support Requesting Technical Information or SupportNEW Product Limited Warranty Falcon ELECTRIC, INCFN SeriesTM UPS Plus 3kVA 12kVA FN SeriesTM UPS Plus 4kVA 16kVA FN SeriesTM UPS Plus 5kVA 20kVA FN SeriesTM UPS Plus 6kVA 24kVA