INSTALLATION
Installing the Rail Kit
C A U T I O N
The UPS and EBM are heavy (see page 52). A minimum of two people are required to lift the cabinets into the rack.
NOTE Mounting rails are required for each UPS and EBM cabinet. If mounting rails are not already installed in your rack, contact your local distributor to order rail kits.
To install the rail kit:
1.Adjust the rail size for the depth of your rack.
2.Select the proper holes in the rail for positioning the UPS in the desired location in the rack.
3.Using two M5 washers and two M5 screws, attach the rail to the rear of the rack (see Figure 4).
4.Secure the rail to the front of the rack with two M5 washers and two M5 screws.
5.Repeat Steps 3 and 4 for the other rail.
1 2
Figure 4. Installing the Rail Kit
24EATON Powerware® 5130 Rack/Tower UPS