Eaton Electrical 1250-3000 VA Troubleshooting Guide, Alarm or Condition Possible Cause Action

Page 64

TROUBLESHOOTING

Table 17. Troubleshooting Guide

Alarm or Condition

Possible Cause

Action

 

 

 

When starting the UPS with the button, all the indicators turn on once, the alarm beeps once, and

then indicator remains on.

The remote power-off (RPO)

Set the contact back to its normal position

contact has been activated to

and press the

button to restart.

shut down the UPS and now

 

 

prevents restart.

 

 

The button, μand indicators are on and all the bar graph indicators flash.

The percent load is greater than the set overload level or UPS capacity.

Check the power drawn by the connected devices and disconnect any non-priority devices. Check the overload setting.

The button and indicator

are on and all the bar graph indicators flash.

A critical overload has occurred. If utility power fails, the load will not be protected in Battery mode.

Check the power drawn by the connected devices and disconnect any non-priority devices.

The indicator is on and all the bar graph indicators flash.

A battery fault has been detected during the automatic test.

Replace the battery (see “Replacing Batteries” on page 46).

The indicator alone is on and the alarm sounds continuously.

UPS fault condition. The load is

Contact your service representative.

not supplied.

 

58EATON Powerware® 5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2 www.powerware.com

Image 64
Contents Powerware 5130 Rack/Tower UPS 1250-3000 VA User’s Guide Requesting a Declaration of Conformity Class a EMC Statements Low-Voltage Models Class B EMC Statements High-Voltage ModelsSpecial Symbols Table of Contents Specifications Troubleshooting WarrantyChapter Introduction Backed by worldwide agency approvals N G E R Important Safety InstructionsR N I N G Vigtige Sikkerhedsanvisninger GEM Disse Anvisninger U T I O NSikkerhedsanvisninger R EBelangrijke Veiligheidsinstructies Bewaar Deze Instructies V a R S E LBelangrijke Veiligheidsinstructies V a a RG E L E T Tärkeitä Turvaohjeita Suomi Säilytä Nämä Ohjeet Tarkeita TurvaohjeitaA R a R O I T U SConsignes DE Sécurité Importantes Conserver CES Instructions Consignes de sécuritéWichtige Sicherheitsanweisungen Aufbewaren SicherheitswarnungenR N U N G H T U N GAvvisi di sicurezza R I C O L OV E R T E N Z a T E N Z I O N EViktig Sikkerhetsinformasion Viktige Sikkerhetsinstruksjoner Gjem Disse InstruksjoneneR L I G Instruções DE Segurança Importantes Guarde Estas Instruções R S I K T I GRegulamentos de Segurança I D a D OПредупреждения по мерам безопасности R I G OОпасно Предупреждение ОсторожноL I G R O Advertencias de SeguridadV E R T E N C I a Viktiga Säkerhetsföreskrifter Spara Dessa Föreskrifter E C a U C I Ó NSäkerhetsföreskrifter R aK T I G T Chapter Installation Inspecting the EquipmentChecking the Accessory Kit UPS Accessory KitItemDescription 2U models onlyEBM Accessory Items Additional High-Voltage Model Accessory ItemsVA models only Connecting the UPS Internal Battery Connecting the Internal Battery ConnectorsUPS Setup Rackmount SetupInstalling the Rail Kit Tower Setup Continue to the following section, Installing the UPS Installing the Joining Brackets Installing the UPS UPS Installation with Four EBMsInstalling a Communication Cable Installing the Power and Equipment Cords High-voltage only RPO and ROO Installation RPO/ROO ConnectionContact UPS Rear Panels 1750 VA, Low-Voltage Rear PanelRear Panel Chapter Operation Turning the UPS OnStarting the UPS on Battery Turning the UPS OffOperating Modes UPS Front PanelBattery Mode Additional UPS Features USB PortUSB Port Contact Communication Port optional Pin Number FunctionLoad Segments PowerShare Programmable ReceptacleCustomizing the UPS with the UPS Configuration Tool Function Factory Setting Other Available SettingsMain Output Options Voltage Threshold OptionsUPS Sensitivity Options Battery OptionsUPS On/Off Options UPS and Battery Care Transporting the UPSStoring the UPS and Batteries When to Replace BatteriesReplacing Batteries How to Replace Internal Batteries Unscrew and remove the metal battery cover see Figure How to Replace Extended Battery Modules Recycling the Used Battery or UPS Low-Voltage Model Specifications High-Voltage Model Specifications Weights and DimensionsPower Levels Dimensions WxHxD WeightEBM Model Number Dimensions WxHxD Weight Power ConnectionsModel Environmental and Safety BatteryBattery Runtimes Half Load+1 EBM +2 EBMs +3 EBMs +4 EBMs Full LoadSpecifications Audible Alarms and UPS Conditions Alarm IndicatorsTroubleshooting Guide Alarm or Condition Possible Cause ActionService and Support Desk for the dealer or distributor nearest youTroubleshooting Chapter Warranty Two-Year Limited Warranty US and CanadaWarranty Ten-Year Pro-Rated Limited Warranty US and Canada Warranty Load Protection Guarantee US and Canada Warranty Page 1642017302