INSTALLATION
W A R N I N G
The RPO/ROO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be separated from any hazardous voltage circuits by reinforced insulation.
To install the RPO or ROO switch:
1.Verify that the UPS is off and unplugged.
2.Unscrew and remove the RPO/ROO connector from the RPO/ROO port on the UPS rear panel.
3.Refer to the following table to plan the RPO or ROO behavior:
Contact | RPO |
|
| ROO* |
|
|
|
|
|
Open | UPS shuts down, the |
| indicator | UPS shuts down |
| ||||
|
|
| ||
| illuminates |
|
|
|
|
|
|
|
|
Closed | Normal operation | |
| To return to normal operation, | |
| deactivate the remote external | |
| contact and restart the UPS by | |
| pressing the | button |
UPS starts up (UPS connected to AC power and AC power is available)
NOTE The local button overrides the ROO function.
4.Connect isolated,
60 Vdc maximum, 30 Vac RMS maximum, and 20 mA maximum). Use stranded,
5.Reinstall the RPO/ROO connector to the RPO/ROO port.
6.Verify that the
7.Plug the UPS power cord into a power outlet.
8.Press and hold the button until you hear the UPS beep (approximately one second).
9.Activate the external RPO or ROO switch to test the function. Verify the status change on the UPS front panel.
10.RPO only.
32EATON Powerware® 5130 Rack/Tower UPS