Emerson Process Management MSL600 Transducer connections, Power and other electrical connections

Page 14

 

Installation, Operation & Maintenance Manual

MSL600

IP262/Z0, Rev. AB

February 2012

 

 

3.4 Transducer connections

The MSL600 is housed in an ABS enclosure rated to IP66. The lower section of the housing is for cable connections and the upper part has the LCD and keypad controls.

It is not necessary, or advisable, to remove the lid of the upper part of the enclosure. There are no user serviceable parts inside.

All field wiring connections are accessible by removing the lower lid, which is secured by four screws. Inside the terminal area, all connections are made using screw terminals. All terminal blocks are suitable for wires 0.5mm2 to 2.5mm2 (26 to 12 AWG). Insulation should be stripped back 7.0mm (0.25 inches).

The transducer cable comprises of five wires, see Figure (6), the connections for which are as follows:

White wire

-

Transducer signal wire. This should be connected to the terminal

 

 

 

block marked ‘SENSOR’ and ‘SIG’.

Black wire

-

Transducer 0V wire. This should be connected to the terminal block

 

 

 

marked ‘SENSOR’ and ‘0V’.

Yellow wire

-

Transducer screen wire. This should be connected to the terminal

 

 

 

block marked ‘SENSOR’ and ‘SCN’.

Red wire

-

Temperature compensation positive wire. This should be connected

 

 

 

to the terminal block marked ‘TEMP’ and ‘IN’

Brown wire

-

Temperature compensation 0V wire. This should be connected to

 

 

 

the terminal block marked ‘TEMP’ and ‘0V’.

Figure (6): Transducer cable wiring

All connections to the transducer are intended to be made via the first M20 cable gland (fitted) on the left-hand side, at the bottom of the MSL600 enclosure.

3.5 Power and other electrical connections

(See also section (i), safety precautions)

It is the responsibility of the installer to observe all local regulations and approval requirements, and to use cable to suit the environmental requirements of the particular application.

Prior to applying power to the unit ensure that the two voltage selection switches are set to the appropriate voltage for the installation.

In the event of a fuse needing replacement the user must ensure that the mains input fuse (F1) has a rating of 200mA (F) and the cleaning compressor (F2) has a rating of 1A(T).

Page 14

Image 14
Contents Installation, Operation & Maintenance Manual MSL600Contents MSL600 12.1 12.2Before Operating this Device the Manual should be Read Fully About the MSL600 About this ManualHuman Machine Interface Important MSL600 featuresSelf-cleaning Mounting bracketAs a system LocationRotating bridge Application planningCircular clarifiers Rectangular clarifiers Static bridge Location Installation Preliminary checks Mounting bracket attachmentInstalling the bracket on the bridge Attaching the MSL600MSL600 mounting Power and other electrical connections Transducer connectionsExternal connection terminals Cable extension Programming DisplayContrast viewing angle control Keypad and Menu NavigationSecurity On-line/Off-lineQuick start parameters Tank depth Bottom referenceTransducer self-cleaning Determination of tank depthCurrent output adjust MA current output parametersTransducer out-of-water time AlarmRelay parameters Digital input Main menu item Detailed operationMenu structure Menu Item DescriptionScrolling Direct accessParameter editing Main menu parameters Installation parametersApplication parameters Start On P250 De-sludge parametersDescription P240 Stop On P251Interval P254 Stop If P252Start Time P253 Max Retries P257Cleaning parameters MA output parametersAlarm Action P402 4 0/4-20mA P403Table B Relay Parameter numbers Relay RL1 mode P410 and RL2 mode P420Alarm mode relay RL1 and RL2 parameters P540 to De-sludge mode relay RL1 and RL2 Fault mode relay RL1 and RL2 parameters P560 to P570Set point mode relay RL1 and RL2 On mode relay RL1 and RL2Relay overrides Min ON, Max ON, and Min OFF Display parameters HMIRelay On and Off Points HMI upper, middle, and lower display optionsClear Profile Backlight On/Off P575Clear Trend Log Interval P590 Low Mem Alarm P593Logging parameters Fast log P5911 Alg. Select P620 Parameter values Default Min Max 128 1024Engineering parameters Common algorithm parameters P621 to P629Default Min Max +85 105 185 Parameter values Default Min Max 100 Top Blanking P623Parameter values Default Min Max 9999 Upr S-nat Temp P625 Noise Alrm Lev P622Lwr S-nat Temp P626 Default Min Max +85 185 SoS constant P627Default metric m/s Bottom Blanking P628Significance P630 Parameter values Default Min Max Lost Echo Rnge P633Municipal 1 parameters P630 to P637 Sharp Echo Reject P631Parameter values Default Min Max 255 Parameter values Default Min Max Dirty Mult P636Parameter values Default Min Max Lost Echo Time P637 Noise SD Mult P635Threshld Offset P640 Parameter values Default Min Max 100Municipal 2 parameter P640 Threshold level = Threshld Offset P640 + Noise Level D834Auto Cycle function Load Defaults functionSystem parameters Display testSettings parameters P730 to P737 and Base Units selection Comms parameters P710 to P716PIN parameter P740 Fixed parameters D750 to D753Readings and diagnostics parameters Readings parameters D800 to D834Diagnostics parameters D835 to D852 Min Xdr Temp D852 Speed of Sound D850Max Xdr Temp D851 Technical reference MaintenanceTroubleshooting Transmit pulse and echo processingProgramming chart Sub-menu Level Parameter Title Par No Main Menu OptionProgramming chart … Direct Model No Specification12.1 MSL600 Outputs12.2 MSL603 transducer WeightAdditional specification notes Dimensional drawings MSL600 Bridge mounted unitMSL600 and MSL603 assembly Fitting instructions MSL603 transducer cable extensionParts required MSL600 MSL600 Emerson Process Management Rosemount Measurement