Emerson Process Management MSL600 manual Municipal 1 parameters P630 to P637, Significance P630

Page 40

 

Installation, Operation & Maintenance Manual

MSL600

IP262/Z0, Rev. AB

February 2012

 

 

7.9.3Municipal 1 parameters P630 to P637

When the Municipal 1 algorithm is selected using parameter P620 (page 37), only the following specific parameters need to be adjusted.

7.9.3.1Significance – P630

This parameter is used to select which echo in the echo profile that the Municipal 1 algorithm chooses as the most likely to correspond to the real sludge blanket level.

The algorithm scans the echo profile for echoes. It calculates the mean and standard deviation of amplitudes for these echoes. Depending on the P630 setting, the algorithm can be programmed to select the first significant echo it comes to, measured from the surface of the supernatant or the most significant echo it detects in the entire profile.

The allowed options are:

First

Most (default)

7.9.3.2Sharp Echo Reject – P631

Electrical noise and other types of false echo are characteristically shorter in duration than the real echo from a sludge blanket. This parameter allows fine tuning of the value which the municipal algorithm uses as a window width to separate out these echoes.

Note:

This is a key system parameter and should not be adjusted without asking for advice from Mobrey Measurement.

Parameter values:

Default

Min

Max

8

5

30

7.9.3.3Lost Echo Rnge - P633

The lost echo range is the distance, split equally above and below, that the device will still look for an echo before going to hold last reading as set in lost echo delay (P637).

The parameter P633 is set in number of samples. However, each sample equates to approximately 25mm (1”). Therefore when set with the default value of 24, the device will look for a valid echo in a window 300mm (12”) above and 300mm (12”) below its last valid value. If no valid echo is present, it will hold its last reading for the programmed amount as set in P637.

Parameter values:

Default Min Max

241410

7.9.3.4Threshold – P634

The Municipal 1 algorithm scans the echo profile for echoes. It calculates the mean and standard deviation of amplitudes for these echoes. In order to be significant, the echoes must exceed a threshold value determined in terms of the standard deviation of the echo amplitudes.

The default value is 0.5 standard deviations.

Parameter values:

Default

Min

Max

0.5

0.00

9.99

Page 40

Image 40
Contents Installation, Operation & Maintenance Manual MSL600Contents MSL600 12.1 12.2Before Operating this Device the Manual should be Read Fully About the MSL600 About this ManualImportant MSL600 features Self-cleaningHuman Machine Interface Mounting bracketAs a system LocationCircular clarifiers Application planningRotating bridge Rectangular clarifiers Static bridgeInstallation Preliminary checksLocation Mounting bracket attachmentInstalling the bracket on the bridge Attaching the MSL600MSL600 mounting Power and other electrical connections Transducer connectionsExternal connection terminals Cable extension Programming DisplayContrast viewing angle control Keypad and Menu NavigationSecurity On-line/Off-lineQuick start parameters Tank depth Bottom referenceTransducer self-cleaning Determination of tank depthCurrent output adjust MA current output parametersRelay parameters AlarmTransducer out-of-water time Digital input Detailed operation Menu structureMain menu item Menu Item DescriptionParameter editing Direct accessScrolling Application parameters Installation parametersMain menu parameters De-sludge parameters Description P240Start On P250 Stop On P251Stop If P252 Start Time P253Interval P254 Max Retries P257Cleaning parameters MA output parametersAlarm Action P402 4 0/4-20mA P403Alarm mode relay RL1 and RL2 parameters P540 to Relay RL1 mode P410 and RL2 mode P420Table B Relay Parameter numbers Fault mode relay RL1 and RL2 parameters P560 to P570 Set point mode relay RL1 and RL2De-sludge mode relay RL1 and RL2 On mode relay RL1 and RL2Display parameters HMI Relay On and Off PointsRelay overrides Min ON, Max ON, and Min OFF HMI upper, middle, and lower display optionsClear Trend Backlight On/Off P575Clear Profile Low Mem Alarm P593 Logging parametersLog Interval P590 Fast log P591Parameter values Default Min Max 128 1024 Engineering parameters1 Alg. Select P620 Common algorithm parameters P621 to P629Parameter values Default Min Max 100 Top Blanking P623 Parameter values Default Min Max 9999 Upr S-nat Temp P625Default Min Max +85 105 185 Noise Alrm Lev P622Default Min Max +85 185 SoS constant P627 Default metric m/sLwr S-nat Temp P626 Bottom Blanking P628Parameter values Default Min Max Lost Echo Rnge P633 Municipal 1 parameters P630 to P637Significance P630 Sharp Echo Reject P631Parameter values Default Min Max Dirty Mult P636 Parameter values Default Min Max Lost Echo Time P637Parameter values Default Min Max 255 Noise SD Mult P635Parameter values Default Min Max 100 Municipal 2 parameter P640Threshld Offset P640 Threshold level = Threshld Offset P640 + Noise Level D834Load Defaults function System parametersAuto Cycle function Display testSettings parameters P730 to P737 and Base Units selection Comms parameters P710 to P716PIN parameter P740 Fixed parameters D750 to D753Readings and diagnostics parameters Readings parameters D800 to D834Diagnostics parameters D835 to D852 Max Xdr Temp D851 Speed of Sound D850Min Xdr Temp D852 Maintenance TroubleshootingTechnical reference Transmit pulse and echo processingProgramming chart Sub-menu Level Parameter Title Par No Main Menu OptionProgramming chart … Direct Specification 12.1 MSL600Model No OutputsAdditional specification notes Weight12.2 MSL603 transducer Dimensional drawings MSL600 Bridge mounted unitMSL600 and MSL603 assembly Parts required MSL603 transducer cable extensionFitting instructions MSL600 MSL600 Emerson Process Management Rosemount Measurement