Emerson Process Management MSL600 manual System parameters, Auto Cycle function, Display test

Page 43

Installation, Operation & Maintenance Manual

IP262/Z0, Rev. AB

February 2012

MSL600

7.10 System parameters

These parameters can be used to test the MSL600 hardware.

Note: A full menu structure is shown in section 11.

7.10.1AUTO CYCLE function

The Auto Cycle or Self-Test function has the effect of automatically ramping up the sludge blanket level value between its minimum and maximum values so as to exercise the current output and relays without the actual blanket level changing.

With the unit On-line, this parameter is accessed via SETUP-SYSTEM-TEST-AUTOCYCLE. Once the menu item AUTOCYCLE is entered press ￿￿. The on screen display prompts you to press ￿ to start the AUTOCYCLE.

AUTOCYCLE is stopped by pressing ￿. Press ESC to return to main menu.

A complete cycle is executed in about 100 seconds. It may be paused and re-started using the ￿ arrow key. During Auto Cycle mode, the MSL600 system continues to measure the blanket level in the background.

On exiting the Auto Cycle mode the sludge blanket level immediately takes on the value based on the MSL600 sensor inputs.

7.10.2DISPLAY test

This function allows the user to test all the pixels in the MSL600 display.

The Display Test function displays the product name, full software version number, and exercises all pixels. The MSL600 remains in Display Test mode until the Esc key is pressed. The same data, excluding the test pattern, is displayed at power-up.

7.10.3Current Output test parameters P700 to P702

This function allows the user to test the current output on the MSL600.

7.10.3.14mA Out Adjust - P700

The current output is calibrated in the factory and should not require any adjustment. However, if required, it is possible to adjust the 4mA point using a calibrated meter (see section 5.5).

7.10.3.220mA Out adjust - P701

The current output is calibrated in the factory and should not require any adjustment. However, if required, it is possible to adjust the 20mA point using a calibrated meter (see section 5.5).

7.10.3.3Set Current - P702

It is possible to force the current output to a value to check loop equipment. Any value between 0 and 20mA can be programmed (see section 5.5). When the unit is returned to On Line mode the current output reverts to normal.

7.10.4LOAD DEFAULTS function

The unit can be reset to its factory-default configuration at any time by selecting the Load Defaults menu option. Pressing ￿ loads the default values when in this menu. This action does not change the language setting or the base units selected (metric or imperial).

Page 43

Image 43
Contents MSL600 Installation, Operation & Maintenance ManualContents MSL600 12.2 12.1Before Operating this Device the Manual should be Read Fully About this Manual About the MSL600Mounting bracket Important MSL600 featuresSelf-cleaning Human Machine InterfaceLocation As a systemCircular clarifiers Application planningRotating bridge Static bridge Rectangular clarifiersMounting bracket attachment InstallationPreliminary checks LocationAttaching the MSL600 Installing the bracket on the bridgeMSL600 mounting Transducer connections Power and other electrical connectionsExternal connection terminals Cable extension Display ProgrammingKeypad and Menu Navigation Contrast viewing angle controlOn-line/Off-line SecurityTank depth Bottom reference Quick start parametersDetermination of tank depth Transducer self-cleaningMA current output parameters Current output adjustRelay parameters AlarmTransducer out-of-water time Digital input Menu Item Description Detailed operationMenu structure Main menu itemParameter editing Direct accessScrolling Application parameters Installation parametersMain menu parameters Stop On P251 De-sludge parametersDescription P240 Start On P250Max Retries P257 Stop If P252Start Time P253 Interval P254MA output parameters Cleaning parameters4 0/4-20mA P403 Alarm Action P402Alarm mode relay RL1 and RL2 parameters P540 to Relay RL1 mode P410 and RL2 mode P420Table B Relay Parameter numbers On mode relay RL1 and RL2 Fault mode relay RL1 and RL2 parameters P560 to P570Set point mode relay RL1 and RL2 De-sludge mode relay RL1 and RL2HMI upper, middle, and lower display options Display parameters HMIRelay On and Off Points Relay overrides Min ON, Max ON, and Min OFFClear Trend Backlight On/Off P575Clear Profile Fast log P591 Low Mem Alarm P593Logging parameters Log Interval P590Common algorithm parameters P621 to P629 Parameter values Default Min Max 128 1024Engineering parameters 1 Alg. Select P620Noise Alrm Lev P622 Parameter values Default Min Max 100 Top Blanking P623Parameter values Default Min Max 9999 Upr S-nat Temp P625 Default Min Max +85 105 185Bottom Blanking P628 Default Min Max +85 185 SoS constant P627Default metric m/s Lwr S-nat Temp P626Sharp Echo Reject P631 Parameter values Default Min Max Lost Echo Rnge P633Municipal 1 parameters P630 to P637 Significance P630Noise SD Mult P635 Parameter values Default Min Max Dirty Mult P636Parameter values Default Min Max Lost Echo Time P637 Parameter values Default Min Max 255Threshold level = Threshld Offset P640 + Noise Level D834 Parameter values Default Min Max 100Municipal 2 parameter P640 Threshld Offset P640Display test Load Defaults functionSystem parameters Auto Cycle functionComms parameters P710 to P716 Settings parameters P730 to P737 and Base Units selectionFixed parameters D750 to D753 PIN parameter P740Readings parameters D800 to D834 Readings and diagnostics parametersDiagnostics parameters D835 to D852 Max Xdr Temp D851 Speed of Sound D850Min Xdr Temp D852 Transmit pulse and echo processing MaintenanceTroubleshooting Technical referenceSub-menu Level Parameter Title Par No Main Menu Option Programming chartProgramming chart … Direct Outputs Specification12.1 MSL600 Model NoAdditional specification notes Weight12.2 MSL603 transducer MSL600 Bridge mounted unit Dimensional drawingsMSL600 and MSL603 assembly Parts required MSL603 transducer cable extensionFitting instructions MSL600 MSL600 Emerson Process Management Rosemount Measurement