| Technical data | 17(86) | ||
4.3 Technical data |
|
|
|
| |
|
|
|
|
|
|
| Mains | Input voltage Uin | 208...240 V; 380...500 V; 525...690 V; |
|
|
| connection | Input frequency | 45...66 Hz |
|
|
|
| Connection to mains | Once per minute or less (normal case) |
|
|
| Motor | Output voltage |
|
| |
| connection | Continuous output current | IH: Ambient temperature max. +50ºC, |
|
|
|
|
| overload 1.5 x IH (1min/10min) |
|
|
|
|
| IL: Ambient temperature max. +40ºC, |
|
|
|
|
| overload 1.1 x IL (1min/10min) |
|
|
|
|
|
|
|
|
|
| Starting torque | 150% (Low overload); 200% (High overload) |
|
|
|
| Starting current | 2.5 x IH 2 secs every 20 secs, if output frequency <30Hz |
|
|
|
|
| and temperature of heatsink <+60ºC (up to 400 kW) |
|
|
|
|
|
|
|
|
|
| Output frequency | 0...320 Hz (NXS); 7200 Hz (Special) |
|
|
|
| Frequency resolution | 0.01 Hz (NXS); Application dependent (NXP) |
|
|
| Control | Control method | Frequency Control U/f |
|
|
| characteristrics |
| Open Loop Sensorless Vector Control |
|
|
|
|
| Closed Loop Frequency Control |
|
|
|
|
| Closed Loop Vector Control (NXP only) |
|
|
|
|
|
|
|
|
|
| Switching frequency | Up to and including NX 0061: |
|
|
|
| (See parameter 2.6.9) | 1...16 kHz; Factory default 10 kHz |
|
|
|
|
| From NX 0072: |
|
|
|
|
| 1...10 kHz; Factory default 3.6 kHz |
|
|
|
|
|
|
|
|
|
| Frequency reference |
|
|
|
|
| Analogue input | Resolution 0.1% (10bit), accuracy ±1% |
|
|
|
| Panel reference | Resolution 0.01 Hz |
|
|
|
| Field weakening point | 30...320 Hz |
|
|
|
| Acceleration time | 0...3000 sec |
|
|
|
| Deceleration time | 0...3000 sec |
|
|
|
| Braking torque |
|
| |
| Ambient | Ambient operating |
|
| |
| conditions | temperature |
|
| |
|
| Storage temperature |
|
| |
|
| Relative humidity | 0 to 95% RH, |
|
|
|
|
| no dripping water |
|
|
|
| Air quality: |
|
|
|
|
| - chemical vapours | IEC |
|
|
|
| - mechanical particles | IEC |
|
|
|
| Altitude | 100% load capacity (no derating) up to 1000m |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Vibration | 5...200 Hz |
|
|
|
| (IEC | Displacement amplitude 3 mm at 5...10.7 Hz |
|
|
|
| Max acceleration amplitude 0.7 G at 10.7...200 Hz |
|
| |
|
|
|
|
| |
|
|
|
|
|
|
|
| Shock | UPS Drop Test (for applicable UPS weights) |
|
|
|
| EN50178, IEC | Storage and shipping: max 15 G, 11 ms (in package) |
|
|
|
| Enclosure class | IP21/NEMA1 standard in entire kW/HP range |
|
|
|
|
| IP54/NEMA12 option in entire kW/HP range |
|
|
|
|
| Note! Keypad installation required for IP54 |
|
|
|
|
|
|
|
|
Table
4