Nx Networks NX series user manual 1786, Characteristrics

Page 17

 

 

Technical data

17(86)

4.3 Technical data

 

 

 

 

 

 

 

 

 

 

 

Mains

Input voltage Uin

208...240 V; 380...500 V; 525...690 V; -15%...+10%

 

 

 

connection

Input frequency

45...66 Hz

 

 

 

 

Connection to mains

Once per minute or less (normal case)

 

 

 

Motor

Output voltage

0—U in

 

 

 

connection

Continuous output current

IH: Ambient temperature max. +50ºC,

 

 

 

 

 

overload 1.5 x IH (1min/10min)

 

 

 

 

 

IL: Ambient temperature max. +40ºC,

 

 

 

 

 

overload 1.1 x IL (1min/10min)

 

 

 

 

 

 

 

 

 

 

Starting torque

150% (Low overload); 200% (High overload)

 

 

 

 

Starting current

2.5 x IH 2 secs every 20 secs, if output frequency <30Hz

 

 

 

 

 

and temperature of heatsink <+60ºC (up to 400 kW)

 

 

 

 

 

 

 

 

 

 

Output frequency

0...320 Hz (NXS); 7200 Hz (Special)

 

 

 

 

Frequency resolution

0.01 Hz (NXS); Application dependent (NXP)

 

 

 

Control

Control method

Frequency Control U/f

 

 

 

characteristrics

 

Open Loop Sensorless Vector Control

 

 

 

 

 

Closed Loop Frequency Control

 

 

 

 

 

Closed Loop Vector Control (NXP only)

 

 

 

 

 

 

 

 

 

 

Switching frequency

Up to and including NX 0061:

 

 

 

 

(See parameter 2.6.9)

1...16 kHz; Factory default 10 kHz

 

 

 

 

 

From NX 0072:

 

 

 

 

 

1...10 kHz; Factory default 3.6 kHz

 

 

 

 

 

 

 

 

 

 

Frequency reference

 

 

 

 

 

Analogue input

Resolution 0.1% (10bit), accuracy ±1%

 

 

 

 

Panel reference

Resolution 0.01 Hz

 

 

 

 

Field weakening point

30...320 Hz

 

 

 

 

Acceleration time

0...3000 sec

 

 

 

 

Deceleration time

0...3000 sec

 

 

 

 

Braking torque

DC-brake: 30%*TN (without brake option)

 

 

 

Ambient

Ambient operating

–10ºC (no frost)... +50ºC: I H

 

 

 

conditions

temperature

–10ºC (no frost)... +40ºC: I L

 

 

 

 

Storage temperature

–40ºC...+70ºC

 

 

 

 

Relative humidity

0 to 95% RH, non-condensing, non-corrosive,

 

 

 

 

 

no dripping water

 

 

 

 

Air quality:

 

 

 

 

 

- chemical vapours

IEC 721-3-3, unit in operation, class 3C2

 

 

 

 

- mechanical particles

IEC 721-3-3, unit in operation, class 3S2

 

 

 

 

Altitude

100% load capacity (no derating) up to 1000m

 

 

 

 

 

1-% derating for each 100m above 1000m; max. 3000m

 

 

 

 

 

 

 

 

 

 

Vibration

5...200 Hz

 

 

 

 

(IEC 721-3-3, EN50178/

Displacement amplitude 3 mm at 5...10.7 Hz

 

 

 

 

EN60068-2-6, IEC68-2-6

Max acceleration amplitude 0.7 G at 10.7...200 Hz

 

 

 

 

(68-2-34, -35, -36)

 

 

 

 

 

 

 

 

 

 

 

Shock

UPS Drop Test (for applicable UPS weights)

 

 

 

 

EN50178, IEC 68-2-27

Storage and shipping: max 15 G, 11 ms (in package)

 

 

 

 

Enclosure class

IP21/NEMA1 standard in entire kW/HP range

 

 

 

 

 

IP54/NEMA12 option in entire kW/HP range

 

 

 

 

 

Note! Keypad installation required for IP54

 

 

 

 

 

 

 

 

Table 4-2. Technical data (continues on next page)

4

Image 17
Contents NX series Start-up Quick Guide Contents NX USER’S Manual Application Manual 486Index 586Control Keypad 686786 SafetySafety instructions = Dangerous voltage = General warning Earthing and earth fault protectionRunning the motor NX frequency converter EMC classification GeneralTechnical criteria Class T 1086Class N Manufacturers declaration of conformity1186 EU Declaration of ConformityReceipt of shipment 1286Type designation code Storage1386 MaintenanceWarranty Introduction Technical data1486 1586 1 NX5 Mains voltage 380-500 Power ratings1686 Characteristrics 17861886 Technical dataMounting Installation1986 NX dimensions, IP21 2086 InstallationNX dimensions, IP21 with collar, FR4 to FR6 Installation 2186Opening needed for the collar installation, FR4 to FR6 2286 InstallationNX dimensions, IP21 with collar, FR7 and FR8 Installation 2386Opening needed for the collar installation, FR7/FR8 2486 InstallationCooling 25862686 Power lossPower loss as function of switching frequency 2786 Power loss as function of switching frequency 0038…0061NX5Cabling and connections Power unit2886 2986 External RFI-filter Filter OptionMains cable Power connectionsMotor cable Control cableCable and fuse sizes 31863286 Installation instructions3386 Stripping lengths of motor and mains cables 34863586 NX frequency converter frames and installation of cablesNX, FR5. Protection class IP21 3686NX, FR6. Protection class IP21 378610. NX, FR7. Protection class IP21 3886Cable and motor insulation checks Cable installation and the UL standards3986 Control connections 4086Control unit 4186 NXOPTA1Galvanic isolation barriers Control cables4386 Control terminal signals4486 Digital input signal inversions+24V Ground +24V4586 Jumper block AI1 mode AI2 modeControl keypad 4686Indications on the Keypad display Drive status indications See control keypad4786 See .3.4, Active FaultsControl place indications See control keypad Status LEDs green green red See control keypad4886 Keypad push-buttons ResetButton descriptions SelectNavigation on the control keypad 5186 No editingMonitoring menu M1 5286Parameter menu M2 53865486 P1 P18 Select the keypad as the active control place by keeping Keypad control menu M3Selection of control place Control placeKeypad direction Keypad reference5886 Active faults menu M4Fault types 5986 Fault type symbol Meaning6086 Fault codes6186 Fault code Possible cause Correcting measures6286 Fault time data record6386 Fault history menu M5System menu M6 6486Functions in the System menu 65866686 Code Function Min Max Unit Default Cust SelectionsLanguage selection 6786Application selection 6886 System settings6986 ChangeEnable ChangeDisabl7086 Connected Not connExample Keypad settings7186 7286 Keypad settings DefaultParameter copy 738620. Storing and loading of parameter sets 7486Parameter comparison 7586Information submenu 7686Counters menu 7786Trip counters submenu 7886Expander board menu M7 7986G1 G2 AutoFurther keypad functions 8086Commissioning of the frequency converter Commissioning8186 8286 8386 8486 Fault tracing8586 Bulgaria