Installation | 25(86) |
5.2 Cooling
Enough free space should be left around the frequency converter to ensure sufficient air circulation and cooling. The required dimensions for free space are in the table below.
If several units are mounted above each other the required free space equals C + D (see figure below). Moreover, the outlet air used for cooling by the lower unit must be directed away from the inlet air to be used by the upper unit.
| Type |
| Dimensions |
|
| ||
|
| A | A2 | B |
| C | D |
| 20 |
| 20 |
| 100 | 50 | |
| 20 |
| 20 |
| 120 | 60 | |
| 30 |
| 20 |
| 160 | 80 | |
| 80 |
| 80 |
| 300 | 100 | |
| 20 | 200 | 80 |
| 300 | 200 | |
|
|
| (150*) |
|
|
|
|
|
|
|
|
|
|
|
|
Table 5-6. Mounting space dimensions
A= clearance around the freq. converter (see also A2 and B)
A2 = clearance needed on either side of the frequency converter for fan change (without disconneting the motor cables)
*= min. clearance for fan change (without disconnecting the
motor cables) between two frequency converters
B= distance from one frequency converter to another or distance to cabinet wall
C= free space above the frequency converter
D= free space underneath the frequency converter
A
A2
C
B | B | |
|
|
|
A
A2
D |
NK5_2
|
| Figure |
|
|
|
| Type | Cooling air required [m3/h) |
|
| |
| 70 | |
|
| |
|
| |
| 190 | |
|
| |
|
| |
| 425 | |
| 0085 NX_6 |
|
| 425 | |
| ||
|
| |
| 650 | |
| ||
|
| |
Table |
|