Nx Networks NX series user manual 4386, Control terminal signals

Page 43

Cabling and connections

43(86)

6.2.2Control terminal signals

 

 

 

 

 

 

 

 

 

 

 

Terminal

Signal

Technical information

 

 

1

 

+10 Vref

Reference voltage

Maximum current 10 mA

 

 

 

 

 

 

 

 

 

 

 

2

 

AI1+

Analogue input,

Selection V or mA with jumper block X1 (see page 45):

 

 

 

 

 

voltage or current

Default: 0– +10V (Ri = 200 k

)

 

 

 

 

 

 

 

(-10V…..+10V Joy-stick control, selected with a jumper)

 

 

 

 

 

 

0– 20mA (Ri = 250

)

 

 

 

3

 

GND/AI1–

Analogue input common

Differential input if not connected to ground;

 

 

 

 

 

 

Allows ± 20V differential mode voltage to GND

 

 

4

 

AI2+

Analogue input,

Selection V or mA with jumper block X2 (see page 45):

 

 

 

 

 

voltage or current

Default: 0– 20mA (Ri = 250

)

 

 

 

 

 

 

0– +10V (Ri = 200 k

)

 

 

 

 

 

 

(-10V…..+10V Joy-stick control, selected with a jumper)

 

 

5

 

GND/AI2–

Analogue input common

Differential input if not connected to ground;

 

 

 

 

 

 

Allows ± 20V differential mode voltage to GND

 

 

6

 

24 Vout

24V auxiliary voltage

± 15%, maximum current 250mA (all boards total);150mA

 

 

 

 

(bidirectional)

 

(from single board); Can also be used as external power

 

 

 

 

 

 

backup for the control unit (and fieldbus)

 

 

7

 

GND

I/O ground

Ground for reference and controls

 

 

 

 

 

 

 

 

 

 

 

8

 

DIN1

Digital input 1

Ri = min. 5k

 

 

 

 

9

 

DIN2

Digital input 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

DIN3

Digital input 3

 

 

 

 

 

 

 

 

 

 

 

 

11

 

CMA

Digital input common A for

Must be connected to GND or 24V of I/O terminal or

 

 

 

 

 

DIN1, DIN2 and DIN3.

to external 24V or GND

 

 

 

 

 

 

 

 

Selection with jumper block X3 (see page 45):

 

 

12

 

24 Vout

24V auxiliary voltage

Same as terminal #6

 

 

 

 

 

 

(bidirectional)

 

 

 

 

 

 

13

 

GND

I/O ground

Same as terminal #7

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

DIB4

Digital input 4

 

 

 

 

 

 

Ri = min. 5k

 

 

 

 

15

 

DIB5

Digital input 5

 

 

 

 

 

16

 

DIB6

Digital input 6

 

 

 

 

 

17

 

CMB

Digital input common B for

Must be connected to GND or 24V of I/O terminal or

 

 

 

 

 

DIB4, DIB5 and DIB6

to external 24V or GND

 

 

 

 

 

 

 

 

Selection with jumper block X3 (see page 45):

 

 

18

 

AO1+

Analogue signal (+output)

Output signal range:

 

 

 

 

 

 

 

 

Current 0(4)–20mA, RL max 500or

 

 

19

 

AO1–

Analogue output common

 

 

 

 

 

 

Voltage 0—10V, R L >1k

 

 

 

 

 

 

 

 

Selection with jumper block X6 (see page 45):

 

 

20

 

DO1

Open collector output

Maximum Uin = 48VDC

 

 

 

 

 

 

 

 

Maximum current = 50 mA

 

 

 

 

 

 

NXOPTA3

 

 

 

 

 

 

21

 

RO1/1

Relay output 1

Maximum switching voltage 250VAC, 125VDC

 

 

 

 

 

 

Maximum switching current8A/24VDC,

 

 

22

 

RO1/2

 

 

 

 

 

 

 

 

0.4A/250VDC

 

 

23

 

RO1/3

 

 

 

 

 

 

Min. switching load

5V/10mA

 

 

 

 

 

 

 

 

25

 

 

Relay output 2

Maximum switching voltage 250VAC, 125VDC

 

 

 

RO2/1

 

Maximum switching current8A/24VDC, 0.4A/250VDC

 

 

26

 

RO2/2

 

Min. switching load

5V/10mA

 

 

28

 

TI1/1

Thermistor input 1

Basic galvanic isolation

 

 

 

 

29

 

TI1/2

 

Double isolation when connected to thermistor

 

 

 

 

 

 

 

 

 

 

Table 6-5. Control I/O terminal signals

6

Image 43
Contents NX series Start-up Quick Guide Contents NX USER’S Manual Application Manual 486Index 586Control Keypad 686Safety instructions Safety786 Running the motor Earthing and earth fault protection= Dangerous voltage = General warning Technical criteria GeneralNX frequency converter EMC classification Manufacturers declaration of conformity 1086Class T Class N1186 EU Declaration of ConformityStorage 1286Receipt of shipment Type designation codeWarranty Maintenance1386 1486 Technical dataIntroduction 1586 1686 Power ratings1 NX5 Mains voltage 380-500 Characteristrics 17861886 Technical data1986 InstallationMounting NX dimensions, IP21 2086 InstallationNX dimensions, IP21 with collar, FR4 to FR6 Installation 2186Opening needed for the collar installation, FR4 to FR6 2286 InstallationNX dimensions, IP21 with collar, FR7 and FR8 Installation 2386Opening needed for the collar installation, FR7/FR8 2486 InstallationCooling 2586Power loss as function of switching frequency Power loss2686 2786 Power loss as function of switching frequency 0038…0061NX52886 Power unitCabling and connections 2986 External RFI-filter Filter OptionControl cable Power connectionsMains cable Motor cableCable and fuse sizes 31863286 Installation instructions3386 Stripping lengths of motor and mains cables 34863586 NX frequency converter frames and installation of cablesNX, FR5. Protection class IP21 3686NX, FR6. Protection class IP21 378610. NX, FR7. Protection class IP21 38863986 Cable installation and the UL standardsCable and motor insulation checks Control unit 4086Control connections 4186 NXOPTA1Galvanic isolation barriers Control cables4386 Control terminal signals+24V Digital input signal inversions4486 +24V Ground4586 Jumper block AI1 mode AI2 modeDrive status indications See control keypad 4686Control keypad Indications on the Keypad displayStatus LEDs green green red See control keypad See .3.4, Active Faults4786 Control place indications See control keypad4886 Select ResetKeypad push-buttons Button descriptionsNavigation on the control keypad 5186 No editingMonitoring menu M1 5286Parameter menu M2 53865486 P1 P18 Control place Keypad control menu M3Select the keypad as the active control place by keeping Selection of control placeKeypad direction Keypad referenceFault types Active faults menu M45886 5986 Fault type symbol Meaning6086 Fault codes6186 Fault code Possible cause Correcting measures6286 Fault time data record6386 Fault history menu M5System menu M6 6486Functions in the System menu 65866686 Code Function Min Max Unit Default Cust SelectionsApplication selection 6786Language selection 6886 System settings6986 ChangeEnable ChangeDisabl7086 Connected Not conn7186 Keypad settingsExample 7286 Keypad settings DefaultParameter copy 738620. Storing and loading of parameter sets 7486Parameter comparison 7586Information submenu 7686Counters menu 7786Trip counters submenu 7886Auto 7986Expander board menu M7 G1 G2Further keypad functions 80868186 CommissioningCommissioning of the frequency converter 8286 8386 8486 Fault tracing8586 Bulgaria