Safety

1.3 Earthing and earth fault protection

The NX frequency converter must always be earthed via a conductor connected to the earthing

terminal .

The earth fault protection inside the frequency converter protects only the converter itself against earth faults in the motor or the motor cable.

If fault current protective switches (e.g. RCD or Earth Leakage devices) are to be used in conjunction with the frequency converter, they must be tested with earth fault currents that are possible to arise in fault situations.

1.4 Running the motor

Warning symbols

For your own safety please pay special attention to the instructions marked with the following symbols:

WARNING

=Dangerous voltage

=General warning

MOTOR RUN CHECK LIST

 

1

Before starting the motor, check that the motor is mounted properly

 

and ensure that the machine connected to the motor allows the

 

 

 

 

motor to be started.

 

2

Set the maximum motor speed (frequency) according to the motor

 

and the machine connected to it.

 

 

 

3

Before reversing the motor shaft rotation direction make sure that

WARNING

this can be done safely.

 

 

4

Ensure that no power correction capacitors are connected to the

 

motor cable.

 

 

 

5

Ensure that the motor terminals are not connected to mains

 

potential.

 

 

Image 8
Contents NX series Start-up Quick Guide Contents NX USER’S Manual 486 Application Manual586 Index686 Control Keypad786 SafetySafety instructions = Dangerous voltage = General warning Earthing and earth fault protectionRunning the motor NX frequency converter EMC classification GeneralTechnical criteria 1086 Class TClass N Manufacturers declaration of conformityEU Declaration of Conformity 11861286 Receipt of shipmentType designation code Storage1386 MaintenanceWarranty Introduction Technical data1486 1586 1 NX5 Mains voltage 380-500 Power ratings1686 1786 CharacteristricsTechnical data 1886Mounting Installation1986 2086 Installation NX dimensions, IP21Installation 2186 NX dimensions, IP21 with collar, FR4 to FR62286 Installation Opening needed for the collar installation, FR4 to FR6Installation 2386 NX dimensions, IP21 with collar, FR7 and FR82486 Installation Opening needed for the collar installation, FR7/FR82586 Cooling2686 Power lossPower loss as function of switching frequency Power loss as function of switching frequency 0038…0061NX5 2786Cabling and connections Power unit2886 External RFI-filter Filter Option 2986Power connections Mains cableMotor cable Control cable3186 Cable and fuse sizesInstallation instructions 32863386 3486 Stripping lengths of motor and mains cablesNX frequency converter frames and installation of cables 35863686 NX, FR5. Protection class IP213786 NX, FR6. Protection class IP213886 10. NX, FR7. Protection class IP21Cable and motor insulation checks Cable installation and the UL standards3986 Control connections 4086Control unit NXOPTA1 4186Control cables Galvanic isolation barriersControl terminal signals 4386Digital input signal inversions 4486+24V Ground +24VJumper block AI1 mode AI2 mode 45864686 Control keypadIndications on the Keypad display Drive status indications See control keypadSee .3.4, Active Faults 4786Control place indications See control keypad Status LEDs green green red See control keypad4886 Reset Keypad push-buttonsButton descriptions SelectNavigation on the control keypad No editing 51865286 Monitoring menu M15386 Parameter menu M25486 P1 P18 Keypad control menu M3 Select the keypad as the active control place by keepingSelection of control place Control placeKeypad reference Keypad direction5886 Active faults menu M4Fault types Fault type symbol Meaning 5986Fault codes 6086Fault code Possible cause Correcting measures 6186Fault time data record 6286Fault history menu M5 63866486 System menu M66586 Functions in the System menuCode Function Min Max Unit Default Cust Selections 6686Language selection 6786Application selection System settings 6886ChangeEnable ChangeDisabl 6986Connected Not conn 7086Example Keypad settings7186 Keypad settings Default 72867386 Parameter copy7486 20. Storing and loading of parameter sets7586 Parameter comparison7686 Information submenu7786 Counters menu7886 Trip counters submenu7986 Expander board menu M7G1 G2 Auto8086 Further keypad functionsCommissioning of the frequency converter Commissioning8186 8286 8386 Fault tracing 84868586 Bulgaria